50
EL250RT
No. CODE DESCRIPTION
6-POSITION
TERMINAL BLOCK
1
GND
Power supply negative
2 T
Battery test. By applying 5V you can check whether the battery has an
output voltage >11.4Vdc. This information is given on the "
B
” terminal.
3
B
High impedance output if the voltage supplied by the battery is <11.4Vdc.
120
Ω
output if the battery voltage is >11.4Vdc.
This information is valid if "
T
" is active.
4 15
High impedance output if the voltage from the power supply is <12.4Vdc.
120
Ω
output if the voltage from the power supply is >12.4Vdc.
5
24
High impedance output if the voltage from the transformer on the "
24Vin
"
terminals is <18Vac.
120
Ω
output if the voltage from the transformer on the "
24Vin
” terminals is
>18Vac.
6 NC
Not connected
TERMINAL NO. DESCRIPTION
8-POSITION
TERMINAL BLOCK
(Power supply
connectors)
1-2
19 Vac: Input to be connected to the transformer
3-4
13.8 Vdc: Output for the infrared power supply
5-6
24 Vac: Input to be connected to the transformer
7-8
24 Vac: Output to be connected to the heaters