PRI-32
H
Imax
I
15-18
LED
Un
Warning
Technical parameters
Function
Supply circuit
Supply terminals:
Supply voltage:
Consumption:
Max. dissipated power
(Un + terminals):
Supply voltage tolerance:
Measuring circuit
Current range:
Current adjustment:
Accuracy
Setting accuracy (mechanical):
Repeat accuracy:
Temperature dependancy:
Limit values tolerance:
Overload capacity:
Output
Number of contacts:
Rated current:
Switching capacity:
Output indication:
Other information
Operating temperature:
Storage temperature:
Electrical strength:
Operating position:
Mounting:
Protection degree:
Overvoltage cathegory:
Pollution degree:
Max. cable size (mm
2
):
Dimensions:
Weight:
Standards:
A1 - A2
AC 24 - 240 V, DC 24 V (AC 50 - 60 Hz)
max. 25 VA / 1.5 W
2 W
-15 %; +10 %
1 - 20 A (AC 50 Hz)
potentiometer
5 %
< 1 %
< 0.1 % / °C
5 %
max. 100 A / 10 s
1x changeover / SPDT (AgNi / Silver Alloy)
8 A / AC1
2000 VA / AC1, 240 W / DC
red LED
-20 °C to 55 °C (-4 °F to 131 °F)
-30 °C to 70 °C (-22 °F to 158 °F)
4 kV (supply - output)
any
DIN rail EN 60715
IP40 from front panel / IP10 terminals
III.
2
solid wire max. 2x 2.5 or max. 1x 4,
with sleeve max. 1x 2.5 or max. 2x 1.5 (AWG 12)
90 x 17.6 x 80.5 mm (3.5˝ x 0.7˝ x 3.2˝)
75 g (2.6 oz.)
EN 60255-6, EN 61010-1
H - Hysteresis
Monitoring relay PRI-32 is determined for control of current level in one phase AC cir-
cuits. Fluent adjustment of access current level predestines this device for many various
applications. Output relay is in normal state off . By overpassing of adjusted current level
relay is closed. An advantage of this relay is universal supply. It is possible to control a
load that does not have consistent supply as PRI-32.
The device is constructed to be connected into 1-phase main and must be installed in
accordance with regulations and norms applicable in a particular country. Installation,
connection and setting can be done only by a person with an adequate electro-technical
qualifi cation which has read and understood this instruction manual and product func-
tions. The device contains protections against over-voltage peaks and disturbing ele-
ments in the supply main. Too ensure correct function of these protection elements it is
necessary to front-end other protective elements of higher degree (A, B, C) and screen-
ing of disturbances of switched devices (contactors, motors, inductive load etc.) as it is
stated in a standard. Before you start with installation, make sure that the device is not
energized and that the main switch is OFF. Do not install the device to the sources of ex-
cessive electromagnetic disturbances. By correct installation, ensure good air circulation
so the maximal allowed operational temperature is not exceeded in case of permanent
operation and higher ambient temperature. While installing the device use screwdriver
width approx. 2 mm. Keep in mind that this device is fully electronic while installing.
Correct function of the device is also depended on transportation, storing and handling.
In case you notice any signs of damage, deformation, malfunction or missing piece, do
not install this device and claim it at the seller. After operational life treat the product as
electronic waste.