ELKHART BRASS URFA-20 Installation And Operating Instructions Manual Download Page 6

municipal supply pressure at the design flow rate, less piping friction loss and elevation 
loss. 

2.  Turn to the appropriate valve performance chart.  The valve model and flow range for 

each graph is indicated in the title at the top of the graph.  Be sure to use the correct 
graph for the designed flow rate through the valve. 

3.  Locate the valve inlet residual pressure on the vertical axis of the chart and draw a line 

from the pressure horizontally across the chart. 

4.  Locate the desired valve outlet residual pressure on the chart horizontal axis and draw a 

vertical line from this pressure across the chart 

5.  From the intersection of the inlet and outlet pressure lines constructed in (3) and (4) 

above, move horizontally to the nearest valve performance curve (actually straight 
diagonal lines).  This will be the appropriate valve setting for the chosen location. 

6.  Determine the valve static inlet pressure.  This will be the sum of the municipal supply 

static pressure plus the pump churn pressure, less the elevation loss. 

7.  To determine the valve static outlet pressure, refer to the appropriate static chart.  

Locate the valve static inlet pressure on the vertical axis of the chart.  Follow across to 
the appropriate valve curve and drop down to the horizontal axis to read valve outlet 
static pressure. 

8.  If static outlet pressure is found to exceed the maximum outlet pressure allowed by 

NFPA 13 or NPFA 14, it will be necessary to re-select a valve setting to the left of the 
originally chosen type. 

 

 

 
 

 

 
 
 
 

SETTING PRESSURE REDUCTION 

 
1.  Remove the tamper-resistant screw from the clear cover by means of tamper-resistant Allen 

wrench provided with valve. 

2.  Insert adjustment tool provided with valve through the slot in the clear cover into the hole 

in the adjustment cylinder. 

3.  Rotate adjustment cylinder until the top of the adjustment cylinder is aligned with desired 

mark on the Indication Label (refer to Figure 1). 

4.  Once rotation limit is reached during adjustment remove the adjustment tool from the 

adjustment cylinder hole and re-insert the adjustment tool into the next available hole.  

ADJUSTMENT CYLINDER 
TOP 

SETTING “A” 

SETTING “E” 

Figure - 1

Summary of Contents for URFA-20

Page 1: ...URFA 20S 2 5 URFA 20 2 5 URFA 25 2 5 INSTALLATION AND OPERATING INSTRUCTIONS FOR FIELD ADJUSTABLE PRESSURE REDUCING CONTROLLING VALVES URFA 20 2 5 MODEL SHOWN...

Page 2: ...UTOFF OPEN CLOSE INDICATION SUPERVISORY SWITCH ENCLOSURE SUPERVISORY SWITCH PLUG TAMPER RESISTANT COVER TAMPER RESISTANT SCREW INDICATION LABEL UPPER BONNET ADJUSTMENT CYINDER HOLE BONNET NUT LOWER BO...

Page 3: ...s where supply riser pressures exceed 175 psi The URFA valves are Listed by Underwriters Laboratories as Special System Water Control Valves Pressure Reducing and Pressure Control Type VLMT and also m...

Page 4: ...ld be selected to provide an outlet pressure not exceeding 165 psi at the maximum inlet pressure 5 Upon system completion each Valve must be tested under both flow and no flow conditions to verify tha...

Page 5: ...independent operation of the valve stem from the manual close push rod this allows for the operator to bypass the large torque required to overcome the stiffness of the adjustment spring INSTALLATION...

Page 6: ...the pump churn pressure less the elevation loss 7 To determine the valve static outlet pressure refer to the appropriate static chart Locate the valve static inlet pressure on the vertical axis of th...

Page 7: ...valve is not manually in the fully opened position refer to NFPA 13 for more details on supervisory requirements An optional supervisory switch assembly with UL approval for use with URFA valves is av...

Page 8: ...gnal Also ensure that the manual handwheel may be fully closed without interference from the supervisory switch assembly VALVE CARE MAINTENANCE URFA valves require minimal maintenance However a routin...

Page 9: ...ve incorrect valve setting it should be reset to the proper setting and undergo flow and no flow testing to verify proper pressure reduction is obtained Flow test results should be compared to previou...

Reviews: