ELKHART BRASS URFA-20 Installation And Operating Instructions Manual Download Page 3

 
SPECIFICATIONS 

 

• 

Pressure rated up to 400 psi. 

• 

Flow rated up to 500 GPM 

• 

Open-Close indication from 2 view directions 

• 

Pressure reduction can be field adjusted 

• 

Pressure reduction adjustment can be easily determined by indication label 

• 

Pressure reduction adjustment has tamper resistant feature 

• 

Low-torque manual close handwheel 

• 

Built-in automatic check valve 

• 

Regulates pressure under both flow and no-flow conditions 

• 

Tapped for pressure gauge on both inlet and outlet side of valve 

• 

Optional integral supervisory switch (For Indoor Use Only) 

 

 

INLET – OUTLET CONNECTIONS 
 

VALVE MODEL 

INLET THREAD 

OUTLET THREAD 

URFA-20-2.5 2-1/2" 

FEMALE 

NPT 

2-1/2" FEMALE NPT 

URFA-20S-2.5 2-1/2" 

FEMALE NPT 

2-1/2" FEMALE NPT 

URFA-25-2.5 

2-1/2" FEMALE NPT 

2-1/2" MALE HOSE 

 
APPLICATION 

 

A.  AUTOMATIC SPRINKLER SYSTEMS 

 

The models URFA-20S-2.5 and URFA-20-2.5 valves are most commonly used in automatic 
sprinkler systems as floor control valves in high-rise buildings where supply riser pressures 
exceed 175 psi.  The URFA valves are Listed by Underwriters Laboratories as “Special System 
Water Control Valves – Pressure Reducing and Pressure Control Type (VLMT)”, and also 
meet the listing requirements for indicating valves.  Installation requirements for pressure 
reducing valves in automatic sprinkler systems are given in Section 4-6.1.2 of NFPA 13, 
Standard for the installation of Sprinkler Systems, 1999 Edition.  When designing URFA 
pressure reducing valves into a sprinkler system a maximum flow rate of 400 GPM should be 
observed. 
 
URFA Pressure Reducing Valves are also listed as  checking devices, which eliminates the 
need for a separate check valve.  When sprinklers on a given floor are fed from dual risers, the 
URFA valve acts as a check valve to prevent loss of sprinkler water supply in the event of one 
riser sustaining damage. 
 
Requirements for Alarm Attachments are given in Section 5-15.1.6 of NFPA 13, Standard for 
the installation of Sprinkler Systems, 1999 Edition.  An integral, listed supervisory alarm 
switch is available on URFA pressure reducing valves as option number “01” when ordering. 

Summary of Contents for URFA-20

Page 1: ...URFA 20S 2 5 URFA 20 2 5 URFA 25 2 5 INSTALLATION AND OPERATING INSTRUCTIONS FOR FIELD ADJUSTABLE PRESSURE REDUCING CONTROLLING VALVES URFA 20 2 5 MODEL SHOWN...

Page 2: ...UTOFF OPEN CLOSE INDICATION SUPERVISORY SWITCH ENCLOSURE SUPERVISORY SWITCH PLUG TAMPER RESISTANT COVER TAMPER RESISTANT SCREW INDICATION LABEL UPPER BONNET ADJUSTMENT CYINDER HOLE BONNET NUT LOWER BO...

Page 3: ...s where supply riser pressures exceed 175 psi The URFA valves are Listed by Underwriters Laboratories as Special System Water Control Valves Pressure Reducing and Pressure Control Type VLMT and also m...

Page 4: ...ld be selected to provide an outlet pressure not exceeding 165 psi at the maximum inlet pressure 5 Upon system completion each Valve must be tested under both flow and no flow conditions to verify tha...

Page 5: ...independent operation of the valve stem from the manual close push rod this allows for the operator to bypass the large torque required to overcome the stiffness of the adjustment spring INSTALLATION...

Page 6: ...the pump churn pressure less the elevation loss 7 To determine the valve static outlet pressure refer to the appropriate static chart Locate the valve static inlet pressure on the vertical axis of th...

Page 7: ...valve is not manually in the fully opened position refer to NFPA 13 for more details on supervisory requirements An optional supervisory switch assembly with UL approval for use with URFA valves is av...

Page 8: ...gnal Also ensure that the manual handwheel may be fully closed without interference from the supervisory switch assembly VALVE CARE MAINTENANCE URFA valves require minimal maintenance However a routin...

Page 9: ...ve incorrect valve setting it should be reset to the proper setting and undergo flow and no flow testing to verify proper pressure reduction is obtained Flow test results should be compared to previou...

Reviews: