ELKHART BRASS URFA-20 Installation And Operating Instructions Manual Download Page 5

to the pressure on the downstream side of the valve.  Because the piston, main stem and valve 
seat float freely from the manual valve stem and handwheel assembly, the valve is able to self-
close under static conditions and maintains a reduced pressure both under no-flow and flowing 
conditions Valve discharge pressure is transmitted to the top side of the piston through pressure 
passages in the main stem.  The presence of the piston results in a net area differential, which 
produces a hydraulic balancing force in the closed direction.  The magnitude of this balancing 
force is in direct proportion to the hydraulic area of the piston. 
 
The Field Adjustable feature of the valve is controlled by a spring within the valve upper 
bonnet.  The spring adds an opening force to the main stem so that pressure reduction may be 
changed as the spring force is changed.   This feature allows for the valve to satisfy all 
expected inlet/outlet pressure ratios.  The Field Adjustable feature allows for one type of valve 
to be specified for all locations in a structure.  Once installed the valves can be adjusted to the 
correct pressure reduction ratio based on their locations.  
 
The URFA valves feature a patent pending manual close design that allows for extremely low 
torque of the handwheel while manually opening and closing the valve.  The unique design 
allows for the for independent operation of the valve stem from the manual close push-rod; this 
allows for the operator to bypass the large torque required to overcome the stiffness of the 
adjustment spring. 

 
INSTALLATION OF VALVE 

 

• 

The valve should first be plumbed into the system 

• 

The upper bonnet may be rotated for optimized access to adjustment window 

Loosen Bonnet Nut 

Rotate Upper Bonnet to desired location of adjustment window 

Apply service removable thread lock to the Bonnet Nut threads 

Tighten the Bonnet Nut firmly 

• 

See wire diagram for proper installation of supervisory switch 

• 

The system should be slowly filled with water and purged of air 

• 

The system should then be flushed to remove any debris 

 

VALVE SETTING SELECTION 

 
The URFA valves have settings of A, B, C, D, and E.  Each valve setting corresponds to a 
pressure reduction graph located at the end of this manual.  The valve setting is determined by 
where the top of the adjustment cylinder lines up on the Adjustment Identification Label 
located on the main stem (refer to Figure 1).  To determine the correct setting for each URFA 
valve in the system design please use the following step. 
 

1.  Determine the standpipe or sprinkler riser residual pressure for each valve location.  

This is the inlet pressure at each valve under design flow conditions.  In order to 
accurately determine these pressures, complete water supply date will be required, 
including results of municipal supply, flow test, and the pump performance curve.  The 
URFA inlet pressure will be equal to the sum of the pump discharge pressure and the 

Summary of Contents for URFA-20

Page 1: ...URFA 20S 2 5 URFA 20 2 5 URFA 25 2 5 INSTALLATION AND OPERATING INSTRUCTIONS FOR FIELD ADJUSTABLE PRESSURE REDUCING CONTROLLING VALVES URFA 20 2 5 MODEL SHOWN...

Page 2: ...UTOFF OPEN CLOSE INDICATION SUPERVISORY SWITCH ENCLOSURE SUPERVISORY SWITCH PLUG TAMPER RESISTANT COVER TAMPER RESISTANT SCREW INDICATION LABEL UPPER BONNET ADJUSTMENT CYINDER HOLE BONNET NUT LOWER BO...

Page 3: ...s where supply riser pressures exceed 175 psi The URFA valves are Listed by Underwriters Laboratories as Special System Water Control Valves Pressure Reducing and Pressure Control Type VLMT and also m...

Page 4: ...ld be selected to provide an outlet pressure not exceeding 165 psi at the maximum inlet pressure 5 Upon system completion each Valve must be tested under both flow and no flow conditions to verify tha...

Page 5: ...independent operation of the valve stem from the manual close push rod this allows for the operator to bypass the large torque required to overcome the stiffness of the adjustment spring INSTALLATION...

Page 6: ...the pump churn pressure less the elevation loss 7 To determine the valve static outlet pressure refer to the appropriate static chart Locate the valve static inlet pressure on the vertical axis of th...

Page 7: ...valve is not manually in the fully opened position refer to NFPA 13 for more details on supervisory requirements An optional supervisory switch assembly with UL approval for use with URFA valves is av...

Page 8: ...gnal Also ensure that the manual handwheel may be fully closed without interference from the supervisory switch assembly VALVE CARE MAINTENANCE URFA valves require minimal maintenance However a routin...

Page 9: ...ve incorrect valve setting it should be reset to the proper setting and undergo flow and no flow testing to verify proper pressure reduction is obtained Flow test results should be compared to previou...