To set the Room, Corridor and Timing Options
a)
Open battery cover at rear and remove paper tab from battery area to enable the remote.
b)
You must turn lights OFF with the remote first to operate and program in this mode. To do this, point the remote control at
the Elkay easyDALi PIR & press the override off button. While in override off the Elkay easyDALi PIR LED flashes white.
c)
To begin installer mode, remove battery cover at rear and place pin in hole and press once. Once feed back light
goes RED you have initiated the Installation Option on the remote.
d)
You will automatically be in the DEFAULT mode of Room Mode 6, which gives 20 minutes ON with 10 minutes dimmed and
then switches off (if no presence detected) This is highlighted in Table 1.
e)
By pressing the MODE UP and – DOWN you will scroll through the room and corridor modes.
When you push the button UP or DOWN you should press once only and observe and count the coloured flashes on the
PIR. The number and colour of flashes corresponds to the Room Timing or the Corridor Timing Options shown in Table 1.
Corridor Options flash RED on the PIR and Room Modes flash GREEN on the PIR. For example, press the mode + button
once and the PIR will flash GREEN four times indicating it is now in Room Option 5. To go back to the DEFAULT setting
press the mode - button once and the PIR will flash GREEN 3 times returning the PIR to the default setting. Scrolling up or
down one press at a time moves you through the options in Table 1.
Corridor Option
ON
DIM
OFF
Number of PIR Colour Flashes
Mode UP and DOWN
1
30min
Yes 10%
No
2
20min
Yes 10%
No
3
10min
Yes 10%
No
4
5min
Yes 10%
No
Room Option
ON
DIM
OFF
Number of PIR Colour Flashes
Mode UP and DOWN
5
30min
15min
Yes
6
20min
10min
Yes
PRE-SET FACTORY DEFAULT
7
10min
5min
Yes
8
5min
5min
Yes
A. Feedback LED
- Continuous RED light for 3 minutes (after last button push). It will then revert back to End User mode.
B. Set Button
- Initiates Walk Test only in Installer Mode.
Walk test can be used to test and setup the Elkay easyDALi PIR sensitivity by moving in & out of the PIRs detection range.
The signal LED on the PIR indicates presence by flashing blue and can be used as a basic walk test. During walk test detection
the luminaires will be illuminated to full brightness then after a short delay with no presence detection the luminaires will dim but
not go off. (See Walk Test).
C. Mode Up and Mode Down
– Setting Timing Room Options and Timing Corridor Options
The product is pre-set to a factory default
– Room option 20 minutes on
– Dim to Min Level 10 minutes
– Off
Fitting and operation instructions
TABLE 1
Timing Options selectable in Installer Mode from the Remote Control
Corridor Option
When selecting Corridor Option lights never go off, they will just dim to the selected minimum arc power.
In Corridor Option all
end user remote control functions are disabled except override off.
In corridor option the luminaires will be illuminated to full
brightness while presence is detected. When presence is no longer detected the luminaires will be dimmed after a preset time. The
luminaires will remain dimmed until presence is again detected.
Corridor Shutdown Option
For Facility managers, caretakers and building maintenance teams, there is the ability to turn off corridor mode completely by
pressing the on/off button in Corridor Option which will dim lights to 10% for 10 minutes and then OFF. This may be useful for factory
shutdowns or when office space will be empty for a long period.