Controller MO 36
47
10.7.12 Sequence
pc
: Pressure relief for electromagnetic bolt
When sequence
pc
is activated by button
LERN
, the present selection is displayed. With button
BT
the desired value can be selected. To return to the learning sequence use button
LERN
.
Display Corresponds
to
s1
Pressure relief for electromagnetic bolt is deactivated.
s2
The gate wing pushes in slow mode min. 500ms, but max. 1.000ms, against the
end stop, until the selected force value is passed.
s3
The gate wing pushes in slow mode min. 500ms, but max. 2.000ms, against the
end stop, until the selected force value is passed.
s4
The gate wing pushes in slow mode min. 500ms, but max. 90s, against the end
stop, until the selected force value is passed.
Table 22
10.7.13 Sequence
pd
: Wind blast suppression
WARNING!
Risk of crushing!
Activation of the wind blast suppression results in a delayed reaction on obstacle.
Use the wind blast suppression only, when additional devices like photoelectric barriers or
safety contact profiles are installed at the gate.
It can be chosen to either reverse on obstacle immediately, or to reverse after the selected threshold
value is exceeded for a preset time. A short wind blast or a swinging gate wing do not result in a
reversing.
REMARK!
The selected wind blast suppression time has no effect at the end position.
When sequence
pd
is activated by button
LERN
, the present selection is displayed. With button
BT
the desired value can be selected. To return to the learning sequence use button
LERN
.
Display Corresponds
to
u-
No wind blast suppression. The controller immediately reacts on obstacle.
u1
up to
u9
The wind blast suppression is equal to 1s (for
u1
) up to 9s (for
u9
).
The controller reacts on obstacle only, if detected longer than 1s (for
u1
) up to
9s (for
u9
).
Table 23