background image

Page 2

ELK-6050 Wireless Smoke Detector

WARNING! LIMITATIONS OF SMOKE DETECTORS

y

Wireless smoke detectors are very reliable, but may not work under
all conditions. No fire alarm provides total protection of life or property.
Smoke detectors are not a substitute for life insurance.

y

Smoke Detectors require a source of power to work.

  This

smoke detector will not operate and the alarm will not sound if batteries
are dead or not installed properly.

y

Smoke Detectors may not be heard.  

A sound sleeper or someone

who has taken drugs or alcohol may not awaken if the alarm is installed
outside a bedroom. Closed or partially closed doors and distance can
block sound. This alarm is not designed for the hearing impaired.

y

Smoke Detectors may not always activate and provide warning
early enough.

 Smoke detectors only activate when enough smoke

reaches the alarm. If a fire starts in a chimney, wall, roof, on the other
side of closed doors, or on a different level of the property, enough
smoke may not reach the alarm for it to alarm.

y

Smoke Detectors are a significant help in reducing loss, injury and even
death. However, no matter how good a detection device is, nothing
works perfectly under every circumstance and we must warn you that
you cannot expect a smoke alarm to ensure that you will never suffer
any damage or injury.

y

Current studies have shown smoke detectors may not awaken all
sleeping individuals. It is the responsibility of individuals in the household
that are capable of assisting others to provide assistance to those who
may not be awakened by the alarm sound, or to those who may be
incapable of safely evacuating the area unassisted.

WHERE TO INSTALL

Warning: As a minimum requirement, smoke detectors must be installed in
accordance with the National Fire Protection Agency (NFPA) Standard 72,
Chapters 2, 3, and 5, which define the standards for the National Fire Alarm
Code (National Fire Protection Association), Batterymarch Park, MA  02269-
9101).  

Depending on the application, you may need to reference other

chapters of NFPA 72 or NFPA 101.

In addition, observe all local and national

building and electrical codes. See back page for listing of NFPA Guidelines.

When choosing an installation location, consider:

o

Use of structure and type of construction

o

Contents you want to protect and their burning characteristics

o

Human occupancy

o

Total area to be monitored

o

Ceiling height and surface condition

o

Air movement and vent locations

o

Obstructions

o

Deflections

After considering these factors, choose a location:

o

Where the temperature range is between 40° and 100° F (4.4° and
37.8° C).

o

Where the humidity is between 0 and 90% non-condensing.

o

Away from ventilation sources that can prevent smoke from reaching
the smoke alarm.

o

That is at least 5 feet (1.5 m) from bathrooms.

When placing the product on a ceiling, mount it in the center of the room
or hallway, at least 4 inches (10cm) away from any walls or partitions.

When mounting the product on a wall, place it so the top is 4 to 12 inches
(10 to 31cm) below the ceiling.

In rooms with sloped, peaked, or gabled ceilings, place smoke alarms 3
feet (.9 m) down or away from the highest point of the ceiling.

If mounting to suspended ceiling tile, secure the tile with the appropriate
fastener to prevent tile removal.

Smoke detectors are not to be used with alarm guards unless the
combination has been evaluated and found suitable for that purpose.

Note: A smoke detector does not provide warnings for fires resulting from
explosions, smoking in bed, or other furniture; ignition of flammable liquids,
vapors and gasses; and children playing with matches or lighters.

Bedroom 1

Den

Living Room

Kitchen

Basement

1st Floor

In homes basements or multiple levels at least one smoke detector shall be on each level.

A Smoke Detector shall be located in the hallway outside the entrance to any bedroom areas.

In new construction an additional Smoke Detector shall be installed in each sleeping area

2nd Floor

S

S

S

S

Dining

Garage

Master 

Bedroom

Bedroom 2

Bath

S

Master 

Bath

Bedroom 3

S

Bath

S

S

S

S

S

S

S

S

Required Smoke Detector – Absolute Minimum 

Additional Smoke required in new construction and for additional protection

Summary of Contents for ELK-6050

Page 1: ...This document should be left with the owner user Owner User Keep this document in a handy location and refer to it when you have questions about this products functions or features Reading this guide...

Page 2: ...you may need to reference other chapters of NFPA 72 or NFPA 101 Inaddition observealllocalandnational building and electrical codes See back page for listing of NFPA Guidelines When choosing an insta...

Page 3: ...personnel identify the sleeping quarters of these individuals IMPORTANT It is recommend that the Smoke Detector be enrolled added into the Control and a Full Test be performed prior to permanently mou...

Page 4: ...r s Test Silence button but down inside the cavity where the heat sensor is located This LED helps provide a way to verify that the wireless RF communications to the Control The LED will briefly flash...

Page 5: ...lowed before a sensor is declared missing 9 PROGRAMTHEZONEDEFINITION ThismustbedonefromKeypad Menu 5 Zone Definitions for all new enrolled wireless zones Program the zone definition of the 6050 detect...

Page 6: ...If error persists replace smoke sensor 4 7 Smoke sensor is within normal sensitivity range None 8 9 Smoke sensor is becoming too sensitive Verify smoke chamber is snapped down securely Clean smoke se...

Page 7: ...total coverage shall include all rooms halls storage areas basements attics lofts spaces above suspended ceilings and other subdivisions and accessible spaces and the inside of all closets elevator sh...

Page 8: ...how two exits from each room It is important that children be instructed carefully because they tend to hide in times of crisis o Establish one meeting place outside the home Insist that everyone meet...

Reviews: