2018 Indiana Design and Installation Manual
16
www.eljen.com
3.0 Subsurface Bed Design and Installation
3.0.10 DISPERSAL AREA:
Dispersal area requirements are located in
IAC 6-8.3 (58) or ISDH Rule 410 6-10.1
(62).
3.0.11 MINIMUM SLOPE REQUIREMENTS:
Maintain a 3:1 slope or gentler for all slopes off the application area.
3.0.12 SUBSURFACE DRAINS:
If subsurface drains are utilized they must remain 10 feet from the edge of the
system sand perimeter.
3.0.13 SIZING GSF SYSTEMS:
TABLE 4: GSF SUBSURFACE BED SIZING CHART
Soil
Loading
Rate
(gpd/sf)
Minimum Basal Area
Required (Square Feet)
A42
Modules
per Room
B43
Modules
per Room
Bedrooms per House
3
4
5
1.2
252
335
419
6
6
0.75
402
536
670
8
7
0.6
503
670
838
9
8
0.5
603
804
1005
11
9
0.3
1005
1340
1675
12
10
0.25
1206
1608
2010
13
11
Notes:
The Minimum Basal Areas have been adjusted to reflect a 33% reduction in absorption field area.
Any jetted bath tub with a capacity greater than 125 gallons will be treated as an extra bedroom for the system sizing requirements per Rule
410 IAC 6-8.3.
3.0.14 SYSTEM LENGTH AND WIDTH:
Best engineering practices should be used when construction the bed
systems. Rule IAC 6-8.3 (79) (2) and ISDH Rule 410 6-10.1 (87) (b) states the dimensions of the bed shall be as
long and narrow as the site allows.
3.0.15 BED DESIGN
: For beds with less than a 0.5% slope, evenly distribute the bed laterals in the basal area. A
minimum separation distance between laterals for A42’s is 3’ and a minimum separation distance between laterals
of 4’ for B43’s.