32 - EN
V800
FOLD
PAR. DESCRIPTION
RANGE
DEF.
U.o.M.
VAL
OP
tAP
Minimum time that temperature upper threshold is exceeded for alarm activation.
If the HOt threshold is exceed for a time longer than tAP the MOP alarm is activated.
0...255
180
sec
OH
OVERHEATING
OH
OLt
Overheating lower threshold.
0.0...100.0
8.0
°C/°F
OH
OtF
Valve opening freezing timer.
0...1999
0
sec
diS
DISPLAY
diS
PA1
PAssword 1.
When enabled (value other than 0), this is the access key to the User parameters (USr).
0...1999
0
number
diS
ndt
number display type. Display with decimal point.
n = no (integers only); y = yes (display with decimal point).
n/y
Y
flag
diS
CA1
Calibration 1. Saturation probe calibration. Positive or negative temperature value added to the value
read from the overheating probe.
-12.0...12.0
0
°C/°F
diS
CA2
CAlibration 2. Overheating probe calibration. Positive or negative temperature value added to the
value read from the saturation probe.
-12.0...12.0
0
°C/°F
CnF
rEL
Firmware rELease. Device version. Reserved: read-only parameter.
/
/
/
CnF
tAb
tAble of parameters. Reserved: read-only parameter.
/
/
/
The following folders and corresponding parameters are visible from the ID985/V Configuration menu
and not from the IWK/V remote terminal. EE0 refers to driver 1, EE1 to driver 2
EE0/EE1
FSS
Device screen. Read-only parameter.
/
/
number