ID 985/E LX

10/13

PAR.

DESCRIPTION

RANGE

DEFAULT

VALUE*

LEVEL**

U.M.

Display - diS label

LdL

Minimum value that can be displayed

-55.0...302

-50.0

2

°C/°F

HdL

Maximum value that can be displayed

-55.0...302

140.0

2

°C/°F

ddL

Display during defrosting: 
0= displays temperature read by thermostat con-
trol probe 
1= displays temperature read entering defrost
cycle until set point is reached 
2= displays “deF” label during defrosting until set
point is reached 
(or when Ldd expires)

0/1/2

1

1-2

flag

Ldd

Time out for unlocking display (with ddL=2) if
defrosting lasts too long or E07 error occurs

0...255

0

1-2

min

dro   (7)

Select °C or °F to display temperature: 
0= °C 
1= °F

0/1

0

1-2

flag

ddd

Value to be displayed: 
0 = Set point 
1 = probe 1 (thermostat control) 
2 = probe 2 (evaporator) 
3 = probe 3 (display)

0/1/2/3

1

2

num

Ero

Establishes which analogue input to display on the
ECHO including: 0= display of associated device
1=probe 1

2=probe 2 

3=probe 3

4=Set-Point

0...4

1

1-2

num

H11   (6)

Configuration of digital inputs/polarity: 
0= disabled

1 = defrost 

2 = reduced set point

3 = auxiliary 

4 = door switch

5= external alarm 

6= disables storage of HACCP alarms 
7= stand-by (On/Off)

8= maintenance request 

9= HACCP alarm reset

-9...9

0

2

num

H08 

Stand-by operating mode 
0= only display switched off; 
1= display on and controls locked; 
2= display off and controls locked

0/1/2

2

2

num

H12   (6)

Configuration of digital inputs/polarity Same as
H11

-9...9

0

2

num

Configuration- CnF label

H00

Selects probe PTC or NTC 
0= PTC

1= NTC

0/1

1

1-2

flag

H02

Quick activation time for functions with configured
buttons. Not possible for aux
(time expected = 1 second)

0...15

5

2

sec

H06

Button/input aux/door switch light active when
instrument is off

n/y

y

2

flag

NOTE:   At level 1 the folders will only display all the level 1 parameters. At level 2 the folders will only display all the 

level 2 parameters. The level marked 1-2 allows the parameter to be displayed at both levels.

H21

Digital output 1 configurability: 
0= disabled    1= compressor 
2= defrost     3= fans          4= alarm 
5= auxiliary    6= stand-by    7= light 
8= buzzer

9=Defrost 2nd evaporator 

10=Condenser fans

0...10

1

2

num

H22

Digital output 2 configurability Same as H21
(default defrost)

0...10

2

2

num

H23

Digital output 3 configurability Same as H21
(default fans)

0...10

3

2

num

Summary of Contents for ID 985 E

Page 1: ...k folder Pb1 probe 1 value folder Pb2 probe 2 value folder Pb3 probe 3 value folder if present Set setting Access the Machine Status menu press the set button and quickly release it The Set folder lab...

Page 2: ...ing menu in the diS folder If passwords are enabled they will be requested PA1 when entering the Programming menu see the Programming Menu sec tion PA2 in the Cnf folder containing the level 1 paramet...

Page 3: ...elect dif ferent types of defrosting with the para meter dty defrost type defrost execution mode The dty parameter can have these values 0 electrical defrosting the compressor is turned off 1 cycle re...

Page 4: ...or dis play probe probe 3 The temperature limits are defined by the HAL maximum alarm LAL minimum alarm and PbA alarm configuration on probe 1 3 or both parameters MAXIMUM AND MINIMUM TEMPERA TURE AL...

Page 5: ...nputs Serial TTL for Televis or Copy Card con nection Digital outputs 4 outputs on relays first output A SPDT 8 3 A 250Va second and third output B C SPST 8 3 A 250Va fourth output D SPST 5 2 A 250Va...

Page 6: ...sequent switch ons 0 250 0 1 2 min OdO Delay in enabling outputs after start up of instru ment or after a power failure Not active if 0 0 250 0 1 2 min dty Type of defrost 0 electrical defrosting 1 cy...

Page 7: ...e level 1 parameters At level 2 the folders will only display all the level 2 parameters The level marked 1 2 allows the parameter to be displayed at both levels FAd Fan activation intervention differ...

Page 8: ...ling delay dLt is active n y n 2 flag dAd Delay in enabling digital input 0 255 0 2 min dOd Digital input switches off loads n y n 2 flag Att Determines if LAL and HAL are expressed as absolute values...

Page 9: ...display n y y 2 Flag L05 Activation of Master network functions n does not ask Slaves for activation of remote functions y asks Slaves for activation of remote functions Slave n ignores activation of...

Page 10: ...ed set point 3 auxiliary 4 door switch 5 external alarm 6 disables storage of HACCP alarms 7 stand by On Off 8 maintenance request 9 HACCP alarm reset 9 9 0 2 num H08 Stand by operating mode 0 only di...

Page 11: ...1 2 Copy Card Fpr label UL Transfer of parameter map from instrument to Copy Card dL Transfer of parameter map from Copy Card to instrument 1 1 Fr 8 Formatting Cancels all data in the Copy Card 1 NOT...

Page 12: ...r Lin set set set set set set set set set set set set set set set set set set set set set set Programming Menu Diagram PARAMETERS level 1 folders CP dEF FAn AL Lit Lin nad Add diS CnF level 2 folders...

Page 13: ...when the probe temperature is 1 higher than or equal to HAL if Att Ab solute 2 higher than or equal to Set HAL if Att rEl ative if Att Abs olute HAL must be with a sign if Att rEL ative HAL must be on...

Reviews: