background image

EWTQ 905

8/8

Error
- - - -
uuuu
oooo

ErAt

noAt

ErEP

Reason
Probe interrupted
The measured variable is under the probe’s limits (under-range)
The measured variable is over  the probe’s limits  (over-range)

Auto-tuning not possible because the process value is higher (with “Func” =HEAt)
than [SP- |SP/2|] or lower (with “Func” =CooL) than [SP+ |SP/2|].

Auto-tuning not finished within 12 hours

Possible anomaly of the EEPROM memory

ERROR SIGNALLING

Action

Verify the correct connection

between probe and instrument

and then verify the correct func-

tioning of the probe

Restart Auto-tuning when the

process value conditions allow it

Check the working of probe  and

actuator and try again to start

Auto-tuning 

Push key set

ALARMS

Eliwell & Controlli s.r.l.
via dell'Industria, 15 Zona Industriale Paludi
32010 Pieve d'Alpago (BL) ITALY
Tel39 0437 986111
Fac39 0437 989066
Internet http:/www.eliwell.it

1/2004 eng
cod. 9IS23045

In error conditions, the instrument provides an output power as
programmed on par “OPE” and activates the desired alarms, if
the relative parameters “ALni” have been programmed = yES.

44.5

98

48

OUT2

48

ST

AT

OUT1

-

+

=

9.5

SET

EWTQ 905

F

set

MAX 9 mm

PANEL + GASKET

BRACKET TYPE 1

BRACKET TYPE 2

,,,

,,,,

,,,,,

,,,,

,,,

MECHANICAL DIMENSIONS,

PANEL CUT-OUT AND

MOUNTING [MM]

INPUT

tc J 

tc K 

Pt100 (IEC)

PTC (KTY81-121)

NTC (103-AT2)

0..20 mA

4..20 mA

0 ... 50 mV

0 ... 60 mV

12 ... 60 mV

0 ... 1 V

0 ... 5 V

1 ... 5 V

0 ... 10 V

2 ... 10 V

available on

models:

C,E

C,E

C,E

E

E

I

I

C,E

C,E

C,E

V

V

V

V

V

MEASURING RANGE TABLE

input

“dP”= 1, 2, 3

- - - -

- - - -

-199.9 ... 850.0 °C

-199.9 ... 999.9 °F

-55.0 ... 150.0 °C

-67.0 ...302.0 °F

-50.0 ... 110.0 °C

-58.0 ... 230.0 °F

-199.9 ... 999.9 

-19.99 ... 99.99 
-1.999 ... 9.999
-199.9 ... 999.9 
-19.99 ... 99.99 
-1.999 ... 9.999
-199.9 ... 999.9 
-19.99 ... 99.99 
-1.999 ... 9.999
-199.9 ... 999.9 
-19.99 ... 99.99 
-1.999 ... 9.999
-199.9 ... 999.9 
-19.99 ... 99.99 
-1.999 ... 9.999
-199.9 ... 999.9 
-19.99 ... 99.99 
-1.999 ... 9.999
-199.9 ... 999.9 
-19.99 ... 99.99 
-1.999 ... 9.999
-199.9 ... 999.9 
-19.99 ... 99.99 
-1.999 ... 9.999
-199.9 ... 999.9 
-19.99 ... 99.99 
-1.999 ... 9.999
-199.9 ... 999.9 
-19.99 ... 99.99 
-1.999 ... 9.999

MEASURING RANGE

input 

“dP” = 0

0 ... 1000 °C

32 ... 1832 °F

0 ... 1370 °C

32 ... 2498 °F

-200 ... 850 °C

-328 ... 1562 °F

-55 ... 150 °C

-67 ... 302 °F

-50 ... 110 °C

-58 ... 230 °F

-1999 ... 9999

-1999 ... 9999

-1999 ... 9999

-1999 ... 9999

-1999 ... 9999

-1999 ... 9999

-1999 ... 9999

-1999 ... 9999

-1999 ... 9999

-1999 ... 9999

parameter

SenS=

J

CrAl

Pt1

Ptc

ntc

0.20

4.20

0.50

0.60

12.60

0.1

0.5

1.5

0.10

2.10

EWTQ 905 PASSWORD = 381

Summary of Contents for EWTQ 905

Page 1: ...figuration para meters menu Once the desired item has been selected push key set to confirm Selecting OPEr and ConF gives the possibili ty of accessing other menus containing addi tional parameters an...

Page 2: ...with normalised analogue input signals it is first nec essary to program the desired resolution on par dP 0 1 1 0 1 2 0 01 3 0 001 and then on par SSC the value that the instrument must visualise at t...

Page 3: ...Point SP and on the hysteresis HSEt The control works in the following way it deac tivates the outputs when the process value reaches the Set Point and it activates the output 1rEG when the process va...

Page 4: ...matically calculate the fol lowing parameters Pb Proportional Band tcr1 Cycle time of the output 1rEG Int Integral Time dEr Derivative Time FuOC Fuzzy Overshoot Control and for the Double Action PID c...

Page 5: ...of SP EWTQ 905 5 8 LoAb off ON AL1 AL1 PV HiAb HAL1 time off ON AL1 PV time HAL1 off off ON OUT off off ON OUT AL1 SP1 Unit PV SP1 Value change SP1 time min SLor SLor LoAb ABSOLUTE LOW ALARM The alarm...

Page 6: ...for temperature probes tc J K RTD Pt 100 IEC PTC KTY 81 121 990 W 25 C NTC 103AT 2 10KW 25 C or mV sig nals 0 50 mV 0 60 mV 12 60 mV or normal ized signals 0 4 20 mA 0 1 V 0 1 5 V 0 2 10 V Normalized...

Page 7: ...AL1H High threshold band alarm AL1 or Maximum set alarm AL1 for high or low alarm AL1L 9999 9999 20 HAL1 Alarm AL1 hysteresis OFF 9999 1 21 AL1d Activation delay of alarm AL1 OFF 9999 sec OFF 22 AL1i...

Page 8: ...rms if the relative parameters ALni have been programmed yES 44 5 98 48 OUT2 48 ST AT OUT1 9 5 SET EWTQ 905 F set MAX 9 mm PANEL GASKET BRACKET TYPE 1 BRACKET TYPE 2 MECHANICAL DIMENSIONS PANEL CUT OU...

Reviews: