EWRC 300/500 NT
8 - EN
English
PARA. DESCRIPTION
U.M.
RANGE
DEFAULT
dPO
Defrost enabling request from power-on
Determines whether or not the instrument must defrost at power-up
(provided that the temperature measured at the evaporator will allow defrost).
n
(0) = no, does not start defrosting at power-on;
y
(1) = yes, starts defrost at power-on
flag
n/y
n
FANS (FAn)
FSt
Fans lockout temperature; if the value read is greater than
FSt
, the fans will be stopped. The value can
positive or negative
°C/°F
-58.0...302
0.0
FAd
Fans activation differential.
°C/°F
0.1 ... 25.0
0.1
Fdt
Fans activation delay after a defrost cycle.
min
0 ... 250
0
dt
dripping time.
min
0 ... 250
0
dFd
Operating mode of evaporator fans during defrost.
n
(0) = no (it depends on FCO parameter);
y
(1) = yes (fans excluded).
flag
n/y
y
FCO
Evaporator fans operating mode. The status of the fans will be:
A compressor ON fans thermoregulated, A compressor OFF depends on FCO
FCO=0
, fans OFF
FCO=1-2
, fans thermoregulated
FCO=3-4
, fans in duty cycle
Dutycycle
: controlled by way of parameters “
FOn
” and “
FOF
”.
num
0 ... 4
1
ALARMS (ALr)
AFd
Alarms cut-in differential.
°C/°F
0.1 ... 25.0
1.0
HAL
Probe 1 maximum alarm. Temperature value (intended either as distance from setpoint or as an
absolute value based on
Att
) above which the probe will trigger activation of the alarm signal.
°C/°F
LA1...302
5.0
LAL
Probe 1 minimum alarm Temperature value (intended as distance from setpoint or as an absolute
value based on
Att
) beneath which the probe will trigger activation of the alarm signal.
°C/°F
-58.0...HA1
-5.0
PAO
Alarm override time after device is switched on following a power failure.
This parameter refers to high/low temperature alarms LAL and HAL only
hours
0 ... 10
3
dAO
Temperature alarm override time after defrost.
min
0 ... 250
60
tAO
Delay preceding indication of temperature alarm.
This parameter refers to high/low temperature alarms LAL and HAL only
min
0 ... 250
0
DISPLAY parameters (diS)
LOC
LOCk. Setpoint edit lock. The parameter programming menu can still be accessed, and the settings
changed, which means also that the status of this parameter can be changed so as to unlock the
keypad.
n
(0) = No
y
(1) = yes.
flag
n/y
n
PA1
PAssword 1. When enabled (
PA1 ≠ 0
) it is the access key for the
level 1 parameters (
User
).
num
0 ... 250
0
ndt
Display values with decimal point.
n
(0) = No (integers only)
y
(1) = Yes (display with decimal point).
flag
n/y
y
CA1
Calibration of probe Pb1.
Positive or negative temperature value added to the value read by Pb1. This sum is used for both
temperature display and temperature regulation purposes.
°C/°F
-30.0...30.0
0.0
CA2
Calibration of probe Pb2.
Positive or negative temperature value added to the value read by Pb2. This sum is used for both
temperature display and temperature regulation purposes.
°C/°F
-30.0...30.0
0.0
ddL
Display mode during defrost.
0
= Displays the temperature read by probe
1
= Locks the reading at the temperature value registering via the probe when the defrost cycle starts
and until the next time the SEt is reached.
2
= Displays the label
dEF
during defrosting and until the next time the SEt is reached (or until
Ldd
has elapsed).
num
0/1/2
1
CONFIGURATION (CnF)
If one or more parameters present in the folder are changed, the controller
MUST
be switched off and
switched on again.
H00
Selection of type of probe used (Pb1 ... Pb3).
(
0
) = PTC
(
1
) = NTC
num
0/1
(PTC/NTC)
1 (NTC)