7 - EN
EWRC 300/500 NT
English
USER PARAMETERS TABLE
This section describes the most commonly used parameters which are always visible (the access password
PA1
is not enabled by default).
For a description of all other parameters, see the user manual.
NOTE
: the user parameters ARE NOT divided into sub-folders and are always visible. The same parameters are also visible in the respective
folders ‘Compressor’, ‘Fans’, etc. (indicated also here to make the groupings clearer) in the password-protected Installer parameters menu.
PARA. DESCRIPTION
U.M.
RANGE
DEFAULT
SEt
Temperature control SEtpoint
°C/°F
-58.0...302
0.0
COMPRESSOR (CPr)
diF
Activation differential
N.B.: diF cannot be equal to 0.
°C/°F
0 ... 30.0
2.0
HSE
Maximum value that can be assigned to the setpoint.
NOTE: The two setpoints are interdependent: HSE cannot be less than LSE and vice versa.
°C/°F
LSE ... HdL
50.0
LSE
Minimum value that can be assigned to the setpoint.
NOTE: The two setpoints are interdependent: LSE cannot be greater than HSE and vice
versa.
°C/°F
LdL ... HSE
-50.0
OSP
Temperature value to be added algebraically to the Setpoint if reduced set enabled (Economy
function). Enabling can be controlled by a key, function or specially configured digital input.
°C/°F
-30.0 ...
30.0
0.0
Cit
Minimum activation time of compressor before possible deactivation. If
Cit = 0
not active.
min
0 ... 255
0
CAt
Maximum activation time of compressor before possible deactivation. If
CAt = 0
not active.
min
0 ... 255
0
Ont
Controller switch-on time in the event of faulty probe.
- if
Ont
= 1 and
OFt
= 0, compressor stays on permanently (ON).
- if
Ont
> 0 and
OFt
> 0, compressor operates in Duty Cycle mode.
min
0 ... 255
10
OFt
Controller switch-off time in the event of faulty probe.
- if
OFt
= 1 and
Ont
= 0, compressor will always stay off (OFF).
- if
Ont
> 0 and
OFt
> 0, compressor operates in Duty Cycle mode.
min
0 ... 255
10
dOn
Switch-on delay. The parameter indicates that a protection is active on the general compressor relay
actuations. At least the indicated time must elapse between the request and the actual activation of
the compressor relay.
sec
0 ... 255
2
dOF
Delay time after power-off: the delay time indicated must elapse between deactivation of the
compressor relay and the next power-on.
min
0 ... 255
0
dbi
Delay time between power-ons; the delay time indicated must elapse between two consecutive
compressor power-ons.
min
0 ... 255
2
OdO
Delay in activating outputs after the instrument is switched on or after a power failure.
0
= Not active
min
0 ... 255
0
dS2
DEFROST (dEF)
dtY
Defrost mode
0
= Electric defrost (defrost cycle OFF), or compressor not running during defrost.
NOTE
: electrical d air defrost, in the case of fans connected in parallel to the defrost output
relay.
1
= Cycle inversion defrost (hot gas, or compressor on during defrost)
2
= “Free” mode defrost (independent of compressor).
num
0 ... 2
0
dit
Interval between 2 defrost cycles
Interval between the start of two consecutive defrost cycles.
0
= Function disabled (defrost NEVER performed).
hours/mins/
secs
0 ... 255
6 hours
dCt
Defrost interval count mode
0
= Compressor running time (DIGIFROST® method);
defrost active ONLY when the compressor is on.
NOTE
: compressor running hours are counted separately from the evaporator probe (count active also
when evaporator probe missing or faulty).
1
= Appliance running hours; defrost count is always active when machine is on and starts at each
power-up.
2
= Compressor stopped Every time the compressor stops, a defrost cycle is performed according to
parameter
dtY
;
3
= With RTC. defrost at specific times set by parameters
dE1
...
dE8
,
F1
...
F8
.
num
0 ... 3
1
dOH
Defrost cycle enabling delay from request
Delay preceding start of first defrost after call.
min
0 ... 59
0
dEt
Defrost timeout
Determines the maximum defrost time on Evaporator 1.
hours/mins/
secs
1 ... 255
30 min
dSt
Defrost end temperature
Defrost 1 end temperature (determined by evaporator probe 1).
°C/°F
-302.0 ...
1472.0
6.0