13
Regulations
Electromagnetic compatibility: This device complies with Directive 2004/108/EC
Security:
This device complies with Directive 2006/95/EC
Food safety:
This device complies with standard EN 13485 as follows:
- suitable for storage
- application: air
- climate range A
- measurement class 1 in the range from -25°C to 15°C (-13°F to 59°F) (*)
(
* exclusively using Eliwell NTC probes)
NOTE
: The technical data included in this document, related to measurement (range, accuracy, resolution, etc.)
refer to the instrument itself, and not to its equipment such as, for example, sensors. This means, for example,
that sensor(s) error(s) shall be added to the instrument’s one.
TABLE OF PARAMETERS
PAR
.
Liv. DESCRIPTION
SEt
Temperature SEtpoint.
COMPRESSOR
diF
1&2
diFferential. Relay compressor tripping differential. The compressor stops on reaching the Setpoint
value (as indicated by the adjustment probe), and restarts at temperature value equal to the Setpoint
plus the value of the differential. Note:
diF ≠ 0.
HSE
1&2 Higher SEt. Maximum possible setpoint value.
LSE
1&2 Lower SEt. Minimum possible setpoint value.
HC
2 The regulator will go to HOT operating mode (set to ‘H’) or COLD operating mode (set to ‘C’)
OSP
2 Offset Set Point. Temperature Value to be added to the Set-Point if reduced set is enabled
(Economy function).
dOd
2 digital (input) Open door. Digital input that allow you to switch off loads.
Valid if H11 = ±4 (door switch).
n
= does not switch off loads;
y
= switch off loads.
dAd
2 digital (input) Activation delay. Delay time in activating the digital input.
Ont
2 ON time (compressor). Compressor activation time in the event of faulty probe. If OFt=1 and
Ont=0, the compressor is always off, while if OFt=1 and Ont>0 it operated in duty cycle mode.
OFt
2 OFF time (compressor). Compressor deactivation time if probe is faulty. If Ont=1 and
OFt=0, the compressor is always on, while if Ont=1 and OFt>0 it operated in duty cycle mode.