OPEN DOOR ALARM

This alarm is generated when the door is
open for longer than the value specified
in parameter tdO. The door open alarm
is signalled in the alarm folder (AL) and
the LED and alarm relay are switched on.
The OPd label is also displayed. 

The relay can be deactivated by pressing
the silencing button. The LED continues
to flash intermittently and the OPd label
remains in the alarm menu until the
door is closed.

MECHANICAL 
ASSEMBLY

The EWDR 981 is designed to be wall-
mounted (removable brackets) or
mounted on DIN rail (Omega 3). The
unit operates correctly with an ambient
temperature range of between -5 and 55
°C. Units must not be installed in
excessively humid and/or dirty locations.

TECHNICAL DATA

Casing: plastic 4 Din modules
Dimensions: front 70x85 mm, depth
61mm.                             

Mounting: on DIN rail (Omega 3) or
wall-mounted.
Connections: on screw terminal block for

2.5mm

2

conductors

(only one conductor per terminal block
for power connections)
Operating temperature: -5...55°C. 

Storage temperature: -30...85°C.
Operating and storage ambient humidity:
10...90 % RH (non-condensing).
Display: 3   sign 

Analogue inputs: 2 NTC/PTC inputs
(parameter configurable) 

Digital inputs: 2 voltage-free parameter-
configurable digital inputs.      

Serial: TTL for Copy Card

Digital outputs: 1 on relay:
16A 1hp 250V SPDT;

Configurable 12V

c

/24mA output

Resolution: 1 or 0.1°C. 

Accuracy: better than 0.5% of bottom
scale +1 digit 

Consumption: 5VA 

Power supply: 230V

a

ELECTRICAL 
CONNECTIONS

Warning! Always switch off machine
before working on electrical
connections.

The instrument has screw terminal blocks
for connecting cables with a maximum
diameter of 2.5 mm

2

(only one conductor

per terminal block for power
connections): for terminal capacity, see
the label on the instrument. 
The relay outputs are voltage free. 
Do not exceed the maximum current
allowed. For higher loads, use a suitable
contactor. 
Make sure that the power voltage
complies with the device voltage. 
Probes have no connection polarity and
can be extended using an ordinary
bipolar cable (note that if probes are
extended this affects the electromagnetic
compatibility (EMC) of the instrument:
special care must be used when wiring).

The TTL serial cable must be kept
separate from the power cables.

EWDR 981 

3/8

CONDITIONS OF USE

PERMITTED USE

For safety reasons the instrument must
be installed and used in accordance with
the instructions supplied. 
Users must not be able to access parts
with dangerous voltage levels under nor-
mal operating conditions. The device
must be suitably protected from water
and dust depending on the specific
application and only be accessible using
special tools (except for the front key-
pad).
The device is ideally suited for house-
hold use and/or similar use in the refrig-
eration sector and has been tested with
regard to safety in accordance with the
European harmonized reference stan-
dards. It is classified as follows:
• as an automatic electronic control
device to be independently mounted as
regards its construction;
• as a 1 B type operated control device
as regards its automatic operating fea-
tures;
• as a Class A device as regards the cate-
gory and structure of the software.

UNPERMITTED USE

The use of the unit for applications
other than those described above is for-
bidden. It should be noted that the relay
contacts supplied with the device are
functional and therefore exposed to
potential faults. Any protection devices
required to comply with product
requirements or dictated by common
sense due to obvious safety reasons
should be installed externally.

RESPONSIBILITY AND RESIDUAL RISKS

Eliwell shall not be liable for any damages deriving from:

- installation/use other than that prescribed and, in particular, which does not comply
with the safety standards specified in the regulations and/or those given herein;

- use on boards which do not guarantee proper protection against electric shock, water
or dust when assembled;

- use on boards which allow dangerous parts to be accessed without the use of tools;

- tampering with and/or alteration of the product;

- installation/use on boards that do not comply with the standards and regulations in
force.

Signal

Description

OPd

Open door alarm

Summary of Contents for EWDR 981

Page 1: ... main menu level The set point setting folder is also closed when the time out elapses Alarm on If an alarm condition exists when the Machine Status menu is accessed the ALfolder label appears PARAMETER PROGRAMMING MENU Access the menu by pressing the set button for at least 5 seconds The menu structure enables all parameter folders to be divided into two levels All the level 1 folders can be acce...

Page 2: ...eter OFL Y DIAGNOSTICS PROBE ALARMS When one of the probes is outside the nominal operating range or the probe is open or has shorted an alarm is generated if at least one of these conditions persists for at least 10 seconds If at least one of these 3 alarms is signalled the alarm LED and relay are enabled When activated code E1 appears on the display If several alarms are activated at the same ti...

Page 3: ...ded using an ordinary bipolar cable note that if probes are extended this affects the electromagnetic compatibility EMC of the instrument special care must be used when wiring The TTL serial cable must be kept separate from the power cables EWDR 981 3 8 CONDITIONS OF USE PERMITTED USE For safety reasons the instrument must be installed and used in accordance with the instructions supplied Users mu...

Page 4: ... min dbi Delay between switch ons the specified time must elapse between two subsequent switch ons 0 250 0 1 2 min OdO Delay in activating outputs after start up of instru ment or after a power failure Not active if 0 0 250 0 1 2 min dty Type of defrost 0 electrical defrosting 1 cycle reversing defrosting hot gas 2 Free mode defrosting compressor disabled 0 1 2 0 1 2 num dit Period of time elapsin...

Page 5: ...is regulated by Att below which the alarm is activated 50 0 HAL 50 0 1 2 C F PAO 3 Alarm exclusion time after start up of instrument following a power failure 0 10 0 1 2 hours dAO Alarm exclusion time after defrosting 0 999 0 1 2 min EWDR 981 5 8 OAO High and low temperature alarm delay after disabling digital input door closed 0 10 0 2 hours tdO Time out after alarm signal when digital input is d...

Page 6: ...to temperature displayed that is also used by controllers 0 1 2 2 2 num LdL Minimum value that can be displayed 55 0 140 50 0 2 C F HdL Maximum value that can be displayed 50 0 302 140 0 2 C F ddL display during defrosting 0 displays temperature read by thermostat control probe 1 displays temperature read entering defrost cycle until set point is reached 2 displays dEF label during defrosting unti...

Page 7: ...s set to positive values and the parameter LAL is set to negative values LAL 3 Refers exclusively to high and low temperature alarms 4 when changing from C to F or vice versa the set points differentials etc are NOT converted for example set 10 C becomes set 10 F 5 CAUTION positive or negative values change polarity Positive values active input when contact is closed Negative values active input w...

Page 8: ...NG DIAGRAM TERMINALS 1 2 Probe input 1 room probe 1 4 Probe input 3 display or 2nd evaporator probe 5 6 Digital input 1 5 7 Digital input 2 8 9 Auxiliary output 12Vc 20mA E see par H25 alarm default 13 14 Power supply 230Va A TTL input for Copy Card 20 21 22 N O relay output C see par H21 compressor default 19 22 N C relay output C see par H21 compressor default EWDR 981 1 2 4 5 6 7 8 9 10 11 12 1...