EWHT800LX  

 

2 - EN

English

INTRODUCTION

The Coldface EWHT800LX series controls the temperature and humidity of a static or ventilated cold 

room. The curing cycle consists of 1 program with 8 customisable climate profiles. The instrument 

controls positive and negative cold rooms and is capable of managing a double evaporator and con-

denser probes. Coldface has 8 configurable relays, 4

 

low-voltage digital inputs configurable for door 

switch,

 

alarm and pressure.

 

Models are available with clock with yearly calendar and HACCP event 

logging. The instrument can be connected to Televis

System

 via the optional plug-in module. The box 

allows for installation of a power contactor or a disconnecting switch with door lock. 

This summary document contains basic information about the standard models EWHT800LX. For fur-

ther  information  and  different  configurations,  refer  to  the  complete  user  manual  p/n  9MA10024 

which can be downloaded free of charge from the www.eliwell.it website.

MECHANICAL INSTALLATION

Manual 

defrost

Display 

 HACCP alarms 

if function active

Display alarms

if active

Functions menu

LOC keyboard lock

rSE activate reduced Set

rPA Pressure switch alarms

rEd disable HACCP

rHC reset HACCP alarms

nAD Day/Night

Aut Automatic regulation

St Start Climate Profile

rSt Reset Climate Profile

System

info

SP1

-18.9

rtc

18.55

Pb1

-20.6

set

time and date

display

probe values

display

probe values

modifty

SetPoint value

confirm with

1 sec

1 sec

1 sec

3 sec

3 sec

ON / OFF function

Pb2

-20.6

InS

USR

PAr

LitE

SEt

0.0

see manual

see manual

diF

2.00

HSE

50.0

modify

value

confirm

with

SetPoint & Probes

Parameters

NAVIGATION DIAGRAM

• 

Screw the backplate to the wall 

using 4 screws (not supplied) to 

match the holes A...D.

• Shut the door and cover the 

screws with the corresponding plate

• Drill holes in the top (or bot

-

tom) of the backplate to pass the 

high and low-voltage wires through.

Cable clamps must be no bigger 

than size PG29

• Remove the protective plate 

on the right of the door

• Take out the 2 screws supplied 

and then open the cover.

Summary of Contents for Coldface EWHT800LX Series

Page 1: ...EWHT800LX Controllers for cold rooms and curing rooms for on board installation...

Page 2: ...downloaded free of charge from the www eliwell it website MECHANICAL INSTALLATION Manual defrost Display HACCP alarms if function active Display alarms if active Functions menu LOC keyboard lock rSE a...

Page 3: ...3 Heating OUT4 Compressor OUT5 Evaporator fan OUT6 Auxiliary 1 ventilation fans OUT7 Auxiliary 2 destratification fans OUT8 Light Probe inputs default settings Pb1 NTC cold room probe Pb2 NTC defrost...

Page 4: ...lation FansOFF 2 CONDENSERFANS yellow FansON FansOFF 3 VENTILATIONFANS AUXILIARY1 AUX yellow VENTILATIONFANS AUX1ON VENTILATIONFANS AUX1OFF 4 DESTRATIFICATIONFANS AUXILIARY2 AUX yellow DESTRATIFICATIO...

Page 5: ...document in the section Parameters Table 1 Press and hold the SET key for 3 seconds until the display shows PAr Lite 2 Press and release the SET key once more The upper display will show the first pa...

Page 6: ...meter FPt can be either the absolute temperature or the temperature relative to the set point 50 150 6 0 C F Fdt Fan activation delay after a defrosting cycle 0 250 0 min dt Drip time 0 250 0 min dFd...

Page 7: ...tor probe Pb2 set H42 0 and set relay OUT5 parameter H25 6 STANDBY or 0 DISABLED to prevent con tinuous ventilation DEHUMIDIFICATION Digital output OUT1 is configured as dehumidification relay It swit...

Page 8: ...is enabled as 0 10V output F00 4 for piloting an external fan module AUXILIARY AUX1 2 ventilation fans Digital output OUT6 is configured as ventilation fans relay The auxiliary output is activated ma...

Page 9: ...gulation activation of relay AUX1 2 and procedures for completing one STEP and switching to the next By default regulation is disabled and the setpoints are all zero The auxiliary relay is enabled The...

Page 10: ...54 55 56 57 OUT8 OUT7 OUT6 OUT5 H28 H27 H26 H25 2 3 4 5 10 11 12 13 8 9 AUX 1 AUX 1 RS485 connection to TelevisSystem available with optional plug in module only Copy Card Bus Adapter RS 485 TTL AUX...

Page 11: ...nlowerdisplay Theupperdisplaywillshowthevalueread bytheroomprobeexceptinthecaseof probeerrors Checkprobetype H45 Checkwiring 2 3 4 5 wireprobe Replaceprobe AL1 Pb1LOWtemperaturealarm valuereadbyPb1 LA...

Page 12: ...11 H14 DependsondelaysetbyparametertdO RecordingoflabelOPdinfolderALr Regulatorblocked seepara dOA PEA Closedoor Depends on delay set by parameter OAO L01 L15 H01 H15 PEn para meter value default 15 m...

Page 13: ...0 10V 0 10 55mA minimum load resistance 180 Ohm Digital output Buzzer only on models where this is provided Serials 1TTL port for connection to Copy Card 1TTL port for connection toTelevisSystem 1RS...

Page 14: ...e 1B controller in terms of software class and structure as a class A device In terms of connection as a device with flexible external and removable cable with Y connection device with pollution grade...

Page 15: ...one 39 0437 986 111 Facsimile 39 0437 989 066 Sales 39 0437 986 100 Italy 39 0437 986 200 other countries saleseliwell invensyscontrols com Technical helpline 39 0437 986 300 E mail techsuppeliwell in...

Reviews: