Electronic Controller 

1. Safety 

Control 

(1)  Time Delay Safety Control 

 

3 minutes delay for compressor---The compressor is ceased for 3minutes to balance the pressure in the 
refrigeration cycle in order to protect the compressor. 

 

2 minutes delay for 4-way valve---The 4-way valve is ceased for 2 minutes to prevent the 
refrigerant-gas abnormal noise when the HEATING operation is OFF or switch to the other operation 
mode. 

(2)  Indoor Pipe Temperature Sensor Frost Prevention Control 

When the indoor pipe temperature sensor reads 

32

  or below for 5 minutes, the indoor pipe temperature 

sensor frost prevention control starts. The compressor and outdoor fan stop and indoor fan operates at high 
speed for 3 minutes. After that, if the indoor pipe temperature sensor reads  less than 

41

 this control 

prolonged until the indoor pipe temperature sensor reads 

41

 or more. 

(3)  High Temperature Protection Control 

During HEATING operation, the outdoor fan motor and compressor are controlled by the indoor pipe 
temperature to prevent the high temperature of compressor. 
Outdoor fan OFF: when the indoor pipe temperature is 

122℉

Outdoor fan ON: when the indoor pipe temperature is 

118.4

 

Compressor OFF: when the indoor pipe temperature is 

143.6℉

Compressor ON: when the indoor pipe temperature is 

118.4

 

2.  “I Feel” Mode Operation 

(1)  When the “I Feel” mode is selected, the operation mode and initial set temperature are determined by the 

initial room temperature at start-up of the operation except to turn off the air conditioner and operates it 
again. 

(2)  If the mode is change to “I Feel” mode from other mode, the “I Feel” mode doesn’t operate until compressor 

stop for more than 3 minutes. 

 
 

 
 
 
 
 
 
 

 

In the “I Feel” mode , when the controller receives the up or down single of temperature, the set 
temperature can adjust by 

33.8

  upper or lower. The biggest you can adjust by 

35.6

  upper or lower. 

3.  “COOLING” Mode Operation 

(1)  When the COOLING mode is selected without setting temperature, the system will set the set temperature at 

78.8℉

  automatically with the AUTO FAN speed. 

(2) 

When selecting the COOLING mode operation, the system will operate according to the setting by the 
remote controller and the operation is as following: 

 

 
 
 
 

Mode 

Initial room temperature 

COOLING  

DRY 

HEATING for Heat Pump Type   
FAN for Cooling Only Type 

78.8℉

 or more 

68℉

 to 

77

 

Less than 

68

 

Initial set temperature 

75.2℉

 

64.4℉

 

73.4

 

4

Summary of Contents for TAC-09CHSA series

Page 1: ...MANUAL No TE1307 Models TAC 09CHSA TAC 12CHSA TAC 18CHSA TAC 24CHSA 1 IMPORTANT NOTICE 2 OPERATION DETAILS 3 ELECTRICAL SCHEMATIC DIAGRAM 4 EXPLOSION VIEW 5 PARTS LIST WALL MOUNTED SPLIT TYPEAIR COND...

Page 2: ...for the interpretation of this information nor can it assume any liability in connection with its use The information specifications and parameter are subject to change due to technical modification...

Page 3: ...controller 6 2 5 3 7 1 1 1 Air Conditioner Service Manual Operation Details Remote Control The remote controller is not preset as Cooling Only Air Conditioner or Heat Pump by manufacturer Each time af...

Page 4: ...tioner Service Manual REMOTE CONTROLLER The four types of remote controller is as follow GYKQ 05 GYKQ 10e optional GYKQ 11e optional GYKQ 12e optional Note The function of remote controller above is t...

Page 5: ...ressor Outdoor fan OFF when the indoor pipe temperature is Outdoor fan ON when the indoor pipe temperature is 118 4 Compressor OFF when the indoor pipe temperature is Compressor ON when the indoor pip...

Page 6: ...selected without setting temperature the system will set the temperature at automatically with the AUTO FAN speed 2 When selecting the HEATING mode operation the system will operate according to the...

Page 7: ...the IPT is less than for 2 minutes When the defrosting operation time on this condition exceeds 8 minutes it will terminate C After the compressor operates continuously for 20 minutes and the IPT is l...

Page 8: ...he set temperature will be raised by 1 1 hour later and by 2 hour later When selecting HEATING operation with SLEEP mode the set temperature will be dropped by 1 1 hour later and 2 hour later After th...

Page 9: ...d position and then set to the desired angle The positioning is decided as follows When the ON OFF button is pressed When the vane control is change from AUTO to MANUAL When the SWING is finished When...

Page 10: ...ed or a button on the remote controller is pressed and normal operation will start NOTE Do not press the EMERGEMCY Operation switch during normal operation 14 AUTO RESTART Function Option 1 When the i...

Page 11: ...of remoter controller except the signal of shut off When the system checks the voltage is 220V and the delay control is finished it operates at normal again When the indoor fan motor is failure the co...

Page 12: ...TCL Air Conditioner Service Manual Wiring diagram Model TAC 09CHSA Indoor unit Outdoor unit 11...

Page 13: ...Air Conditioner Service Manual Wiring diagram Model TAC 12CHSA TAC 18CHSA Indoor unit Outdoor unit 12...

Page 14: ...Air Conditioner Service Manual Wiring diagram Model TAC 24CHSA Indoor unit Outdoor unit 13...

Page 15: ...Air Conditioner Service Manual Explosion view Model TAC 09CHSA TAC 12CHSA Indoor unit 15 6 11 12 8 10 9 7 5 4 3 2 18 17 16 22 21 19 20 24 23 25 26 27 1 14 13 14...

Page 16: ...Air Conditioner Service Manual Explosion view Model TAC 18CHSA Indoor unit 24 14 13 25 22 20 19 21 23 17 16 15 18 2 3 1 5 6 4 7 9 10 12 11 8 15...

Page 17: ...Air Conditioner Service Manual Explosion view Model TAC 24CHSA Indoor unit 13 14 26 25 27 22 23 19 18 17 16 21 20 24 2 1 3 5 7 6 4 15 9 10 12 11 8 16...

Page 18: ...CB 1 11 Display PCB Box 1 12 Air Filter 2 13 Front Panel 1 Option 14 Display PCB Cover 1 15 Power Supply Cord 1 16 Vane 1 17 Drainage Hose 1 18 Cable Clamp 1 19 Main PCB 1 20 Electrical Box 1 21 Vane...

Page 19: ...Display PCB Box 1 12 Left Air Filter 1 Right Air Filter 1 13 Front Panel 1 14 Display PCB cover 1 option 15 Vane 1 16 Drainage Hose 1 17 Vane Motor 1 18 Sensor Holder 1 19 Main PCB 1 20 Indoor Motor C...

Page 20: ...Box 1 12 Left Air Filter 1 Right Air Filter 1 13 Front Panel 1 14 Display PCB Cover 1 15 Electrical Box Cover 1 16 Vane A 1 17 Vane B 1 18 Drainage Hose 1 19 Cable Clamp 1 20 Vane Motor 2 21 Sensor Ho...

Page 21: ...Air Conditioner Service Manual Explosion view Model TAC 09CHSA TAC 12CHSA Outdoor unit 27 1 26 2 3 4 25 23 24 22 21 19 20 16 17 15 14 18 5 6 7 8 10 9 13 12 11 20...

Page 22: ...Air Conditioner Service Manual Explosion view Model TAC 18CHSA Outdoor unit 27 1 26 2 3 4 25 23 24 22 21 19 20 16 17 15 14 18 5 6 7 8 10 9 13 12 11 21...

Page 23: ...Air Conditioner Service Manual Explosion view Model TAC 24CHSA Outdoor unit 27 1 26 2 3 4 25 23 24 22 21 19 20 16 17 15 14 18 5 6 7 8 10 9 13 12 11 22...

Page 24: ...1 4 way Valve 1 12 4 way Valve Assembly 1 Optional 13 Outdoor Base 1 14 Right Plate 1 15 Two way Valve 1 16 Valve Supporter 1 17 Three way Valve 1 18 Electrical Box Cover 1 19 Outdoor cable Clamp 1 20...

Page 25: ...d It Accessories 1 12 Discharge Pipe 1 Optional 13 Suction Pipe 1 Optional 14 Outdoor Base 1 15 Two way Valve 1 16 Valve Supporter 1 17 Three way Valve 1 18 Right Plate 1 19 Electrical Box Cover 1 20...

Page 26: ...Valve 1 12 4 way Valve Assembly 1 Optional 13 Outdoor base 1 14 Right Plate 1 15 Two way Valve 1 16 Valve Supporter 1 17 Three way Valve 1 18 Electrical Box Cover 1 19 Outdoor Cable Clamp 1 20 Outdoo...

Reviews: