EuroMaster AutoEV
31
x 1/2
x 1
x 2
x 5
RCD type
EN 61008
EN 61009
300mS
300mS
150mS
40mS
General
BS 7671
2000mS
300mS
150mS
40mS
IEC 60364-4-41
999mS
1000mS
150mS
40mS
NEK
400mS
400mS
150mS
40mS
EN 61008
EN 61009
500mS
500mS
200mS
150mS
Selective
BS 7671
2000mS
500mS
200mS
150mS
IEC 60364-4-41
1000mS
1000mS
150mS
40mS
NEK
500mS
500mS
200mS
150mS
Table 6.6.1 Maximum test time related.
x 1/2
x 1
x 2
x 5
I∆n
mA
AC
A
A+6mA
B
AC
A
A+6mA
B
AC
A
A+6mA
B
AC
A
A+6mA
B
10
O
O
O
O
O
O
O
O
O
O
O
O
30
O
O
O
O
O
O
O
O
O
O
O
O
100
O
O
O
O
O
O
O
O
O
O
O
O
300
O
O
O
O
O
O
O
O
O
O
X
X
500
O
O
O
O
O
O
O
O
X
X
X
X
1000
O
O
O
O
O
X
X
X
X
X
X
X
Table 6.6.2 Status by RCD type.
Selective type RCD has a 30 second delay during measurement.
Be aware: Leakage currents in the circuit following the residual
current protection device may influence the measurements
Be aware: The potential fields of other earthing installations may
influence the measurement
Be aware: Equipment, which is connected downstream of a
residual current protective device (RCD) may cause a
considerable extension of the operating time. Examples of such
equipment might be connected capacitors or running motors.
Summary of Contents for EuroMaster AutoEv
Page 1: ...Ver 1 3 ELIT EuroMaster AutoEv Brukermanual User manual page 55 ...
Page 54: ...Euromaster AutoEV 53 ELIT AS Hellenvegen 9 2022 GJERDRUM ...
Page 55: ...EuroMaster AutoEV User s manual Ver 1 0 3 ...
Page 59: ...EuroMaster AutoEV 4 2 Product composition EuroMaster AutoEV Instrument ...
Page 91: ...EuroMaster AutoEV 36 Figure 6 8 5 Earth Resistor 3Pole connection ...