EuroMaster AutoEV
28
I. Set the rotary switch to RCD.
II. Press F1 button to change to Uc.
III. Connect the test leads as shown in Figure 6.6.1.
IV. If there is no problem with the test lead connection, “OK” is displayed as shown in Figure 6.6.4.
V. When “OK” is displayed, press the Test button to perform measurement.
VI. The
symbol being measured is displayed.
VII. When the measurement is complete, the RCD Contact voltage and Ri values are displayed on the
screen.
UC
RCD
10mA
Uc
10.5
V
Ri
1000
Ω
AC
General
0
OK
TN-net
1
230
229
Figure 6.6.5 RCD / Uc Measurement completed.
Calculated as Ri = Uc /
I∆n
RCD type
Contact voltage Uc
Rated I∆n
AC
General
1.05 x I∆n
any
AC
Selective
1.05 x I∆n x 2
A,A+6mA
General
1.05 x I∆n x 1
.4
≥
30mA
A,A+6mA
Selective
1.05 x I∆n x 1.4 x 2
A,A+6mA
General
1.05 x I∆n x 2
< 30mA
A,A+6mA
Selective
1.05 x I∆n x 2 x 2
B
General
1.05 x I∆n x 2
any
B
Selective
1.05 x I∆n x 2 x 2