16
2.3
Wiring Recommendations
Recommended calculated values for CityCharge Mini 2
charging station wires: (When calculated cable length Max:
50 meters; Power factor (cos
φ): 0,95;
voltage drop (%): 7%;
Cabling method: Four single core copper wire in the pipe
(three phase)):
Side A, Power
(kW)
Side B, Power
(kW)
Total Charger
Power (kW)
Amperage per
Phase (A)
Recommended cross
-
section (mm
2
)
3,7 kW
3,7 kW
7,4 kW
16 A
2,5 mm
2
7,4 kW
7,4 kW
14,8 kW
32 A
6 mm
2
11 kW
11 kW
22 kW
32 A
6 mm
2
22 kW
22 kW
44 kW
64 A
16 mm
2
Note that these values are only recommendations, each in-
stallation is different and the cable cross section should be
calculated individually each time.
Warning: failure to select the correct cable cross
-
section may
cause equipment damage or electrical fire.
When using TNS and TNC
-
S systems, it is recommended to
use 5 single core cooper wire. When using TT system with
separate grounding, make sure that the grounding cable cross
-
section match the power supply cable cross
-
section.
The absolute maximum cable cross
-
section must be no
greater than 35mm2. The thicker cable will not fit the cable
terminals inside the charging station.