Connections and Interfaces
- 37 -
10.6.2.3
PROFIBUS Interface
The sensor option profibus is fitted as standard with a profibus interface according to IEC61158 / IEC61784.
The following parameters are specified.
Table 10: Parameter PROFIBUS Interface
PROFIBUS Interface
Transmission
RS485 two-wire line
Wire length
1200 m at 9,6 kBaud
200 m at 1,5 MBaud
100 m at 12 MBaud
Baud rate
9,6 kBaud to 12 MBaud (auto detect)
Clock rate max.
250 kHz
Participants
max. 32 per Segment (with repeater until 126 expandable)
Mono- and Multi-master systems are possible
In delivery status is participant 05 set
10.6.2.4
Pin Assignment
Table 11: Pin Assignment PROFIBUS IN
Table 12: Pin Assignment PROFIBUS OUT
PROFIBUS IN (Flanged Plug M12)
Pin
Function
1
N.C.
2
Data A
3
N.C.
4
Data B
5
Shield
PROFIBUS OUT (Flanged Socket M12)
Pin
Function
1
N.C.
2
Data A
3
N.C.
4
Data B
5
Shield
Table 13: Power Supply
Power supply (Fanged Plug M8)
Pin
Color
Function
1
Brown
+ 10 to 30 VDC
2
White
N.C.
3
Blue
0 V / GND
4
Black
N.C.
Figure 35: Pin Assignment PROFIBUS
Profibus OUT
Profibus IN
Power Supply