User Manual / NDA 100/3 TH(S) RG L20 230AC(PoE) LAN
17
MODBUS Settings for Sensor No.2
Sensor No. 1 Function
3, 4
Function number, which is used for reading temperature and humidity values.
Default: 4. (Default for ELEN sensors.)
Sensor No. 2 Register address for temperature
0 to 65535
Address of register, which contains temperature value.
The temperature value must be signed int and in tenths of °C.
Default: 0. (Default for ELEN sensors.)
Sensor No. 2 Register address for humidity
0 to 65535
Address of register, which contains humidity value.
The humidity value must be signed int and in tenths of %RH.
Default: 10. (Default for ELEN sensors.)
Note: Do not forget to press the
Set
button after making each change.
Otherwise the change will be discarded. When finished with settings, click the
Refresh
button.
Stop bits are set automatically according to parity settings as per MODBUS protocol specifications.
(Valid for all communication interfaces of display.)
It is possible to reset the IP address back to factory default value by pressing and holding the
RESET
button
for
5
seconds. The
RESET
button is located near the external sensor connector P1 on the back panel.
Change administrator password
Enter new password if you want to change it.
Default password is “
admin
”.
Click on the “save new password” button when finished.
Current password
Enter current password.
New password
Enter new password, max. 10 characters.
Confirm new password
Re-enter new password.