Parameter description
Display
Designation
Description
08:03
Switch-off
Setting range:
2K ... (Switch-on differential - 3K)
differential
A
T1
Factory setting:
5K
Function:
If temperate difference between sensors of heat supplier F3 and
heat storage tank F1 is
smaller
than set value, the pump
switches
off
.
08:04 Minimum
pump
Setting
range:
OFF
(----)
running time
A
T1
0.5 ... 60 min
Factory setting:
3 min
Function:
Minimum switch-on time of pump per start.
08:05
Minimum
Setting range:
OFF (----)
temperature heat
5 ... 80°C
supplier
A
T1
Factory setting:
OFF
Function:
Irrespective of switching differentials, the pump switches on
only after the sensor of heat supplier F3 has exceeded the set
value.
08:06
Maximum
Setting range:
OFF (----), 30 ... 110°C
temperature heat
Factory setting:
90°C
supplier
A
T1 Function:
Irrespective of switching differentials, the pump performs a
forced switch on after the sensor of heat supplier F3 has
exceeded the set value.
08:07
Final switch-off
Setting range:
OFF (----), 70 ... 210°C
temperature heat
Factory setting:
OFF
supplier
A
T1
Function:
Irrespective of switching differentials, the pump performs a
forced switch off after the sensor of heat supplier F3 has
exceeded the set value.
08:08
Maximum
Setting range:
OFF (----), 50 ... 110°C
temperature heat
Factory setting:
75°C
storage tank
A
T1 Function:
Irrespective of switching differentials, the pump performs a forced
switch off after the sensor of heat storage tank F1 has exceeded the set
value. This switch-off takes priority over functions 08:07 and 08:06.