Instruction Manual
PS 8000 E 3U Series
Operating the device
6.3 Other control elements
6.3.1 Rotary knobs
Both of the rotary knobs have a push button function. Pushing
any or both of these will effect following:
a) Fine adjustment mode (Fine)
A short push of any of both buttons activates or deactivates the
fine adjustment mode for manual operation. If „Fine“ is active,
all set values, thresholds and limits can be adjusted in smallest
possible steps, no matter what mode is currently active (preset,
memory ect.). It is indicated by the status text „Fine“ in the
status area. Also see section „6.4 Adjusting set values“ below.
b) Device setup
Pushing
both
buttons together for >3s while the output is
off
changes to device setup. It is left the same way.
6.4 Adjusting set values
1. In manual operation
During manual operation, both rotary knobs are used to conti-
nuously adjust the set values of voltage and current from 0%
to 100% nominal value in predefined steps (see table). In order
to set the values for OVP and UVL the button
Preset UVL/OVP
has to pushed once or twice. In order to set the power set value
the button
Preset Power
has to be pushed.
Note
The OVP value can be lower than the voltage set value and
will cause an OV alarm as soon as the output is switched on
and the actual voltage reaches the OVP threshold!
Setting values manually can be done in fine or coarse steps,
whereas coarse is default.
Fine
is required to be activated by
the one of rotary knob pushbuttons and has a step width of 1.
For
coarse
adjustment, following step widths apply in de-
pendency of the nominal values (also refer to technical specs):
Voltage / OVP / UVL
Current
Nom. val. Coarse Fine
Nom. val. Coarse Fine
40V
0.25V
10mV
30A
0.2A
10mA
80V
0.5V
10mV
60A
0.5A
10mA
160V
1V
100mV
70A
0.5A
10mA
200V
2V
100mV
90A
1A
10mA
240V
2V
100mV
120A
1A
100mA
400V
2V
100mV
140A
1A
100mA
500V
5V
100mV
210/250A 2A
100mA
600V
5V
100mV
340A
2A
100mA
1000V
10V
1V
510A
5A
100mA
1500V
10V
1V
Power
Nominal value
Coarse
Fine
3.3/5kW
50W
1W
6.6/10kW
100W
10W
15kW
100W
10W
Note
The resolution of the set value adjustment in some cases is,
depending on the nominal values, higher than the one of the
output voltage. Thus it can happen that the output voltage
only changes every 2 or 3 steps.
2. In remote control via analogue interface
See section „10. Analogue interface“.
3. In remote control via digital interface card