About the device
1. General
1.1 Introduction
The microprocessor controlled power supplies of the
PS 800 R series are designed for wall mount and
are cooled by a temperature-controlled fan.
The functionality focuses industrial power supply.
The device will continue operation after a blackout
with the last settings.
The output voltage is seperated into three selectable
ranges, where each one is defined as approximately
1/3 of the nominal voltage.
The power output is short-circuit-proof and overload-
proof. For protection of the loads, the device also
features an overvoltage protection (OVP). During an
overtemperature (OT) event, the power output will
be switched off until the unit has cooled down and
automatically switched on again.
The device require a two-phase supply with 400V
for correct operation.
1.2 Visual check
After receipt, the unit has to be checked for signs
of physical damage. If any damage is found, the
unit may not be operated. Also contact your dealer
immediately.
1.3 Scope of delivery
1 x Power supply unit
1 x Printed operating guide
1 x Phoenix plug, 2 pole, plugged
1 x Phoenix plug, 4 pole, plugged
2. Installation
2.1 Mounting
The device is designed for vertical wall mount. It is
required to mount it in a way that allows unimpeded
air flow through the ventilation slots. Take care for
plenty of space (at least 15cm) below and above
the device in order to ensure proper cooling. For
the installation dimensions see section „4. Technical
and the drawing from page 20 on.
2.2 Mains connection
The device can be operated at AC input voltages
from 340V to 460V and input frequencies of 50Hz
or 60Hz.
The input connection is done at the 3pole WAGO
clamp terminal „Power Input“ at the bottom side
and according the print.
The input requires a two-
phase grid with L1, L2, PE, 120° phase rotation
and 400V between the phases
.
Clamping procedure:
The input wiring must only be done by trained tech-
nical personnel. Main focus lies on an appropriate
cross section of the mains lead (see technical spe-
cifications for typical input current), as well as the
fact that the device does not feature a power switch.
The input is fused by two standard 6.3x32mm T16A
fuses, which are located in the two fuseholders next
to the input connector.
2.3 DC output connection
The load is connected to the DC output terminals
on the top side, using leads with appropriate cross
section (rec‘d 2.5mm²). The device can produce
dangerous voltages. Thus the output must be co-
vered with the included cover when working with
the device. There are different DC terminal types:
• 80V and 200V
models:
Screw fastening M8 on a plastic DC terminal
Recommendation: ring cable lugs 8mm
• 500V
model:
Screw-clamp terminal, plastic
Recommendation: ring cable lugs 6mm
Summary of Contents for PS 800 R Series
Page 2: ......
Page 8: ...CN 8 PS 800 R 06 22 2018 4 1 4 1...
Page 9: ...CN 9 PS 800 R 06 22 2018 3 2 500V...
Page 10: ...CN 10 PS 800 R 06 22 2018 4...
Page 14: ......
Page 22: ...EN 22 Instruction Manual PS 800 R Series Date 06 22 2018 About the device Figure 4 Side view...
Page 26: ......
Page 27: ......