Analogue interface

All  models  feature  a  12  pin  analogue  interface  on 

the front of the device. It can be used to monitor the 

device condition, as well as remotely start/stop the 

charging procedure. 
Also see next page.

Handling

Powering the device

The device does not feature a power switch. When 

connecting  it  to  mains,  it  is  immediately  ready  to 

work.
After switching mains off the device stores the last 

state (selected mode, output condition) in order to 

restore it automatically at the next start. Thus it can 

continue to work after an interruption like a blackout 

etc.

Adjusting the output voltage

The nominal output voltage is seperated into three 

selectable  voltage  ranges,  each  approximately  1/ 

of the nominal voltage. For details see the „Technical 

specifications“. 

About the device

Technical specifications

PS 880-40R

PS 880-60R

PS 8360-10R

PS 8360-15R

Mains input

Input voltage

90….264V

90….264V

90….264V

90….264V

Frequency

45….65Hz

45….65Hz

45….65Hz

45….65Hz

Power factor correction

>0.99

>0.99

>0.99

>0.99

Input current at 230V and full load

approx. 4.8A

approx. 7.5A

approx. 4.8A

approx. 7.5A

Input current at 100V and full load

approx. 11.4A

approx. 11.4A

approx. 11.4A

approx. 11.4A

Output - Voltage

Nominal voltage U

Nom

80V

80V

360V

360V

Voltage range 1

0V...30V

0V...30V

0V...120V

0V...120V

Voltage range 2

30V...60V

30V...60V

120V...240V

120V...240V

Voltage range 3

60V...80V

60V...80V

240V...360V

240V...360V

Stability at 10-90% load

<0.05%

<0.05%

<0.05%

<0.05%

Stability at ±10%

¨

 U

In

<0.02%

<0.02%

<0.02%

<0.02%

Ripple

<70mV

PP

<70mV

PP

<100mV

PP

<100mV

PP

Regulation 10-100% load

<2ms

<2ms

<2ms

<2ms

Output - Current

Nominal current

40A

60A

10A

15A

Stability at 0-100% 

¨

 U

Out

<0.15%

<0.15%

<0.15%

<0.15%

Stability at ±10%

¨

 U

In

<0.05%

<0.05%

<0.05%

<0.05%

Ripple

<100mA

PP

<100mA

PP

<15mA

PP

<15mA

PP

Output - Power

Nominal power

1000W

1500W

1000W

1500W

Nominal power at U

In

 <150V

1000W

1000W

1000W

1000W

Miscellaneous

Operation temperature

0….40°C

0….40°C

0….40°C

0….40°C

Storage temperature

 -20….70°C

 -20….70°C

 -20….70°C

 -20….70°C

Humidity

<80%

<80%

<80%

<80%

Dimensions (WxHxD)

90x360x240mm

90x360x240mm

90x360x240mm

90x360x240mm

Weight

8.9kg

9.2kg

8.9kg

9.2kg

Article No.

21540107

21540108

21540109

21540110

Safety
EMC standards
Overvoltage category
Protection class

EN 60950

EN 61204, EN 55022 Class B

Class II

Class I

The  built-in  trimmer  is  a  10-turn  type  and  the  ap-

proximate  10  rotations  from  left  stop  to  right  stop 

correspond to the selected range.

Switching output on or off

The pushbutton „On/Off“ is used to switch the power 

output on or off, if not inhibited by any error (OVP or 

OT) or the device being in remote control. The voltage 

set by the trimmer will then be put out immediately.
The output can also be switched off at any time via 

pin 8 „Rem-SB“ of the analogue interface and then 

on again.

Attention! The pin REM-SB overrides the pushbutton 

„On/Off“.

When the output is switched on, the LED „CC“ will 

indicate  constant  current  operation  (LED  is  on)  or 

constant voltage operation (LED is off).

Selecting a voltage range

The pushbutton „Output Range“ is used to select the 

output voltage ranges. The output has to be off in 

order to select the voltage range.

Summary of Contents for EA-PS 800 R

Page 1: ...Netzger te Serie EA PS 800 R 1000W 1500W EA PS 880 40R 21 540 107 EA PS 880 60R 21 540 108 EA PS 8360 10R 21 540 109 EA PS 8360 15R 21 540 110...

Page 2: ......

Page 3: ...uchtigkeit zu sch tzen Der DC Ausgang ist stets vor Ber hrung zu sch t zen Schrumpfschlauch z B da das Ger t ge f hrliche Ausgangsspannungen erzeugen kann Impressum Bedienungsanleitung Netzger te Seri...

Page 4: ...und so zu montieren da ein ungehinderter Luftstrom f r die L fterk hlung gew hrleistet ist Es mu so ange bracht werden da die L ftungsein und ausl sse sich in vertikaler Richtung befinden und mindest...

Page 5: ...en der Betriebszustand des Ger tes die Ausgangsspannung und der Ausgangs strom berwacht werden Siehe auch Seite 7 Leistungsreduzierung Ger te mit 1500W Nennleistung schalten bei Netzein gangsspannunge...

Page 6: ...ng ein und ausschalten Der Taster On Off dient zum Einschalten und Aus schalten des Leistungsausganges falls dies nicht durch anstehende Fehler OT OVP oder Fernsteuerungsbe trieb verhindert wird Die d...

Page 7: ...1V Ein High Uhigh 4V 9 OT OVP DO bertemperatur OT berspannung OVP Low Kein Fehler Ulow 1V High Fehler Uhigh 4V Umax 0V Imax 20mA Quasi Open Collector mit Pull up gegen 15V 10 DGND Bezug f r Digitalsig...

Page 8: ...0 Nennwert gesetzt Clipping Bedienung des Ger tes Sollwerte stellen 1 Analoge Eing nge AI Das Beispiel zeigt die gleichzeitige Ansteuerung von Strom und Spannung ber zwei Potentiometer Die se beziehen...

Page 9: ...Power Supply Series EA PS 800 R 1000W 1500W EA PS 880 40R 21 540 107 EA PS 880 60R 21 540 108 EA PS 8360 10R 21 540 109 EA PS 8360 15R 21 540 110...

Page 10: ......

Page 11: ...ction manual are prohibited and might be follo wed by legal consequences Date February 2009 Safety instructions The cross section of the load leads has to match the nominal current of the device Avoid...

Page 12: ...power factor correction and a wide range input It can be operated at AC input voltages from 90V to 264V and mains frequencies of 45Hz up to 65Hz The connection is done at the 3pole terminal Power Inp...

Page 13: ...0 05 0 05 0 05 0 05 Stability at 10 UIn 0 02 0 02 0 02 0 02 Ripple 70mVPP 70mVPP 100mVPP 100mVPP Regulation 10 100 load 2ms 2ms 2ms 2ms Output Current Nominal current 40A 60A 10A 15A Stability at 0 10...

Page 14: ...in 7 Remote to low If required one of the set values can be bridged to the reference voltage VREF and will thus be 100 Remote control is indicated by the LED External For pin assigment of the analogue...

Page 15: ...ror Uhigh 4V Umax 0V Imax 20mA Quasi Open Collector with pull up to 15V 10 DGND Reference for digital signals For control and monitoring signals 11 Reserved X must not be connected 12 Reserved X must...

Page 16: ...EA Elektro Automatik GmbH Co KG Entwicklung Produktion Vertrieb Helmholtzstra e 31 33 41747 Viersen Telefon 02162 37 85 0 Telefax 02162 16 230 ea1974 elektroautomatik de www elektroautomatik de...

Reviews: