46
© 2006, Elektro-Automatik GmbH & Co. KG
Irrtümer und Änderungen vorbehalten
EN
Instruction Manual
PSI 8000 3U Series
Date: 05-03-2012
About the device
PSI 8500-90 3U
PSI 8600-70 3U
PSI 81500-30 3U
Mains input
Input voltage range
340…460V AC
340…460V AC
340…460V AC
Input voltage range optional
588…796V AC +MP
588…796V AC +MP
588…796V AC +MP
Required phases
L1, L2, L3, PE
L1, L2, L3, PE
L1, L2, L3, PE
Input frequency
50/60Hz
50/60Hz
50/60Hz
Input fuse
6x T16A
6x T16A
6x T16A
Input current
max. 28A
max. 28A
max. 28A
Power factor
> 0.99
> 0.99
> 0.99
Output - Voltage
Nominal voltage U
Nom
500V
600V
1500V
Adjustable range
0V…U
Nom
0V…U
Nom
0V…U
Nom
Stability at mains fluctuation ±10%
∆
U
IN
< 0.02%
< 0.02%
< 0.02%
Stability at 0…100% load
< 0.05%
< 0.05%
< 0.05%
Ramp-up time 10...90% at 100% load
max. 30ms
max. 30ms
max. 30ms
Ripple @ BWL 20MHz
< 300mVpp
< 70mVrms
< 400mVpp
< 80mVrms
< 1000mVpp
< 350mVrms
Accuracy*
≤
0.2%
≤
0.2%
≤
0.2%
Resolution of display
100mV
100mV
1V
Remote sense compensation
max. 10V
max. 18V
max. 30V
Overvoltage protection
threshold (adjustable)
0…550V
0…660V
0…1650V
Output - Current
Nominal current I
Nom
90A
70A
30A
Adjustable range
0…I
Nom
0…I
Nom
0…I
Nom
Stability at mains fluctuation ±10%
∆
U
IN
< 0.05%
< 0.05%
< 0.05%
Stability at 0…100%
∆
U
OUT
< 0.15%
< 0.15%
< 0.15%
Ripple @ BWL 20MHz
< 50mApp
< 23mArms
< 30mApp
< 12mArms
< 19mApp
< 13mArms
Accuracy*
≤
0.2%
≤
0.2%
≤
0.2%
Resolution of display
10mA
10mA
10mA
Transient recovery time 10….90% load
< 2ms
< 2ms
< 2ms
Output - Power
Nominal power P
Nom
15000W
15000W
15000W
Nominal power at derating
0...P
Nom
0...P
Nom
0...P
Nom
Accuracy*
≤
0.2%
≤
0.2%
≤
0.2%
Resolution of display
0.01kW
0.01kW
0.01kW
Efficiency
95.50%
95.20%
95.50%
Miscellaneous
Ambient temperature
0….50°C
0….50°C
0….50°C
Storage temperature
-20….70°C
-20….70°C
-20….70°C
Humidity rel.
< 80%
< 80%
< 80%
Dimensions (WxHxD) **
19" 3U 595mm
19" 3U 595mm
19" 3U 595mm
Weight
33kg
33kg
33kg
Redundancy
yes
no
no
Isooutput to enclosure
500V DC
1000V DC
1000V DC
Isolation -output to enclosure
Isolation input to output
Cooling
Safety
EMC standards
Overvoltage class
Protection class
Pollution degree
Operational altitude
Series operation
max. series connection voltage
Master-Slave
Parallel operation
max. parallel connection voltage
Master-Slave
Analogue programming
Input range
Accuracy
Input impedance
Article number
09230437
09230444
09230439
300V DC
1
2
by fans, air inlet on the front, air exhaust on the rear
EN 60950
EN 61326, EN 55022 Class B
2
4200V DC
no
600V
1500V
yes, via Share bus
<2000m
53kOhm
≤
0.2%
0…5V or 0…10V, selectable
* Related to the nominal value, the accuracy defines the maximum allowed deviation between set value and actual value.
Example: a 80V model has min. 0.2% voltage accuracy. This is 160mV. When setting a voltage of 5V and with an allowed maximum deviation of 160mV, the resulting
actual value could be between 4.84V and 5.16V.
** Enclosure dimensions only, not overall dimensions