6. When mounting horizontally in pipes with free downstream outlet, the flow sensor should be
mounted such that it will always be filled with liquid, for example in a bend situated lower than the
height of the outlet.
In case the liquid is carrying particles, e.g. when measuring sludge,
Sewage etc. the flow sensor must be mounted vertically .
7. When mounting horizontally the flow sensor can be rotated max. +/- 45° seen from the
connection end. If the flow sensor is rotated more than 45°, one of the electrodes may not be in
full contact with the liquid.
Max 45°
Max 45°