![Electron MASTERTEMP Instruction Manual Download Page 23](http://html.mh-extra.com/html/electron/mastertemp/mastertemp_instruction-manual_2385724023.webp)
MONITOR DIGITAL TEMPERATURE - MASTERTEMP
20
SERIAL COMMUNICATION MASTERTEMP
Protocol:
MODBUS RTU or DNP 3 L2
Baud rate: 2400 a 57.600
(Auto Baud Rate)
Data Bits:
8
Parity:
None / Even / Odd
Stop Bits:
1
Variable Type:
Holding Registers (40.000)
Modbus
Address
DNP
Address
Readout Range
Bits
Index
State
Description
Point Name
Write
Read
Scale
2
2
-50.0 – 250.0
-
-
Oil Temperature Alarm
W/R
-1000:10
3
3
-50.0 – 250.0
-
-
Winding 1 Temperature Alarm
W/R
-1000:10
4
4
-50.0 – 250.0
-
-
Winding 2 Temperature Alarm
W/R
-1000:10
5
5
-50.0 – 250.0
-
-
Winding 3 Temperature Alarm
W/R
-1000:10
6
6
0 - 1
-
Register – shutdown due load
-
0
0
For 0, shutdown due load OFF
W/R
-
1
For 1, shudown due load ON
7
7
-50.0 – 250.0
-
-
Oil Temperature Shutdown
W/R
-1000:10
8
8
-50.0 – 250.0
-
-
Winding 1 Temperature Shutdown
W/R
-1000:10
9
9
-50.0 – 250.0
-
-
Winding 2 Temperature Shutdown
W/R
-1000:10
10
10
-50.0 – 250.0
-
-
Winding 3 Temperature Shutdown
W/R
-1000:10
11
11
0 - 3
-
Register – Cooling TypeRegistro
W/R
-
-
1
Cooling Actuation due Temperature
3
Cooling Actuation due Temperature and Load
12
12
-50.0 – 250.0
-
-
Oil Temperature to 1st Cooling Group Actuation
W/R
-1000:10
13
13
-50.0 – 250.0
-
-
Winding 1 Temperature to 1st Cooling Group Actuation
W/R
-1000:10
14
14
-50.0 – 250.0
-
-
Winding 2 Temperature to 1st Cooling Group Actuation
W/R
-1000:10
15
15
-50.0 – 250.0
-
-
Winding 3 Temperature to 1st Cooling Group Actuation
W/R
-1000:10
17
17
-50.0 – 250.0
-
-
Oil Temperature to 2nd Cooling Group Actuation
W/R
-1000:10
18
18
-50.0 – 250.0
-
-
Winding 1 Temperature to 2nd Cooling Group Actuation
W/R
-1000:10
19
19
-50.0 – 250.0
-
-
Winding 2 Temperature to 2nd Cooling Group Actuation
W/R
-1000:10
20
20
-50.0 – 250.0
-
-
Winding 3 Temperature to 2nd Cooling Group Actuation
W/R
-1000:10
21
21
0-100
-
-
Hysteresis for Alarm Deactivation
W/R
-1000:10
22
22
0-100
-
-
Hysteresis for Cooling Deactivation
W/R
-1000:10
23
23
0-20
-
-
Shutdown Delay (minutes)
W/R
1:1
Summary of Contents for MASTERTEMP
Page 1: ...DIGITAL TEMPERATURE MONITOR MASTERTEMP 1 Instructions Manual Manual de Instruções ...
Page 7: ...DIGITAL TEMPERATURE MONITOR MASTERTEMP 4 APPLICATION EXAMPLE ...
Page 8: ...DIGITAL TEMPERATURE MONITOR MASTERTEMP 5 CATALOG CODE DIMENSION ...
Page 9: ...DIGITAL TEMPERATURE MONITOR MASTERTEMP 6 WIRING DIAGRAM MASTERTEMP ...
Page 45: ...MONITOR DIGITAL TEMPERATURE MASTERTEMP 42 EXEMPLO DE APLICAÇÃO ...
Page 46: ...MONITOR DIGITAL TEMPERATURE MASTERTEMP 43 CÓDIGO DE CATÁLOGO DIMENSÕES ...
Page 47: ...MONITOR DIGITAL TEMPERATURE MASTERTEMP 44 DIAGRAMAS DE LIGAÇÃO MASTERTEMP ...