DIGITAL TEMPERATURE MONITOR – MASTERTEMP
15
Rev
1.1
Continuation.... MASTERTEMP CONFIGURATION MENU ACTUA
Submenu
Parameters
Variable
Description
Cooling
Exercise
Exercise
ON / OFF
Configures the cooling exercise.
OFF
– Cooling exercise disabled.
ON
– Cooling exercise enabled.
Frequency
Daily or
Sunday to Saturday
Daily – run the cooling exercise every day.
If selected any other day, the exercise will run weekly.
Initial Time
HH : MM
Time to start the exercise.
Final Time
HH : MM
Time to finish the exercise.
Auxiliary
Relay 1
Function
Option
OFF
Sensor 1
Sensor 2
Winding 1
Winding 2
Winding 3
Indicates which variable will be mirrored on the auxiliary relay 1.
Temperature
-50 to 250 °C
Actuation temperature for auxiliary relay 1.
Delay
ON / OFF
Delay to actuate auxiliary relay 1.
The time of the delay is the same set in Shutdown Setup.
Histeresys
0 to 30 °C
Temperature difference for the deactivation of the auxiliary relay
1.
Exemple
: If the auxiliary relay 1 is set to 90 °C and the
histeresys to 1 °C, the auxiliary relay 1 will be deactivated when
temperature reaches 88.9 °C.
Auxiliary
Relay 2
Function
Option
OFF
Temp Diff
Sensor 1
Sensor 2
Winding 1
Winding 2
Winding 3
Indicates which variable will be mirrored on the auxiliary relay 2.
Temp Diff – reffers to the differential of temperature between
Sensor 1 and Sensor 2. It’s only a valid option in case both
sensors are activated.
Temperature
-50 to 250 °C
Actuation temperature for auxiliary relay 2.
Delay
ON / OFF
Delay to actuate auxiliary relay 2.
The time of the delay is the same set in Shutdown Setup.
Histeresys
0 to 30 °C
Temperature difference for the deactivation of the auxiliary relay
2.
Exemple
: If the auxiliary relay 2 is set to 90 °C and the
histeresys to 1 °C, the auxiliary relay 2 will be deactivated when
temperature reaches 88.9 °C.
Actuation
Return
Oil Alarm
Oil Shutdown
Winding 1 Alarm
Winding 1 Shutdown
Winding 2 Alarm
Winding 2 Shutdown
Winding 3 Alarm
Winding 3 Shutdown
Fail Alarm
Auto
Man.
Configuration for the way how each relay will be put in operation
after its respective actuation (function ANSI 86).
Man.
– Reset is configured to Manual, that is, the actuated
relay will be back to its original state after an operator
intervention. It will be necessary to do the RESET.
AUTO
– the actuated relay will be back to its original state
automatically.
Summary of Contents for MASTERTEMP
Page 1: ...DIGITAL TEMPERATURE MONITOR MASTERTEMP 1 Instructions Manual Manual de Instruções ...
Page 7: ...DIGITAL TEMPERATURE MONITOR MASTERTEMP 4 APPLICATION EXAMPLE ...
Page 8: ...DIGITAL TEMPERATURE MONITOR MASTERTEMP 5 CATALOG CODE DIMENSION ...
Page 9: ...DIGITAL TEMPERATURE MONITOR MASTERTEMP 6 WIRING DIAGRAM MASTERTEMP ...
Page 45: ...MONITOR DIGITAL TEMPERATURE MASTERTEMP 42 EXEMPLO DE APLICAÇÃO ...
Page 46: ...MONITOR DIGITAL TEMPERATURE MASTERTEMP 43 CÓDIGO DE CATÁLOGO DIMENSÕES ...
Page 47: ...MONITOR DIGITAL TEMPERATURE MASTERTEMP 44 DIAGRAMAS DE LIGAÇÃO MASTERTEMP ...