MENU ACTUA
The menu ACTUA configures the actuations of the
MasterTemp
TM
and have the following parameters:
Temperature Alarm
Shutdown Setup
Cooling
Cooling Exercise
Auxiliary Relay 1
Auxiliary Relay 2
Actuation Return
Actuation Test
Cooling Actuation
To access the menu ACTUA, with the display in presentation mode and press key SET, the display will show the
tabs. Use the key ►, navigate to the menu ACTUA and press SET.
This menu have a password and shows a password reminder. Below is
0000
. Use the keys ▲▼ to type the
password and and the key SET to confirm and enter the menu. Case the password is wrong, it will show a message
WRONG PASSWORD and will return to
0000
.
After input the password, the
MasterTemp
TM
will ask it again only when going back to the presentation mode. In
case of continuing on the configuration in other menus, the password will not be requested again.
Originally, the Mastertemp password is 0000. In case of lost or forgetting, get in touch with Electron do Brasil and inform the
Password Reminder.
Navigate by menus, submenus and paratemeters with keys ▲▼◄►. Select the submenu or parameter and press
SET, change the variable with keys ▲▼ and press SET to confirm the changing. If exiting the parameter or submenu
without confirming, the parameters return to previous values.
Submenu
Parameter
Variable
Description
Temperature
Alarm
Oil
Winding 1
Winding 2
Winding 3
-50 to 250
°C
Configuration for the actuation of temperature alarms. When the correspondent
sensor reaches the set temperature, the respective relay is actuated and the
respective LED on the front face is turned on, indicating active alarm.
Oil –
actuates relay 3 (pins 26 and 27);
Winding 1 –
actuates relay 5 (pins 26 e 28).
Winding 2 –
actuates relay 7 (pins 26 e 29).
Winding 3 –
actuates relay 9 (pins 26 e 30).
Histeresys
0,1 to 10 °C
Temperature difference for the deactivation of the alarms.
Exemple
: If the alarm value is set to 90 °C and the histeresys to 1 °C, the alarm
will be deactivated when temperature reaches 88.9 °C. This parameter is valid
for the 4 alarms (oil and the 3 windings).
Summary of Contents for MASTERTEMP
Page 1: ...DIGITAL TEMPERATURE MONITOR MASTERTEMP 1 Instructions Manual Manual de Instruções ...
Page 7: ...DIGITAL TEMPERATURE MONITOR MASTERTEMP 4 APPLICATION EXAMPLE ...
Page 8: ...DIGITAL TEMPERATURE MONITOR MASTERTEMP 5 CATALOG CODE DIMENSION ...
Page 9: ...DIGITAL TEMPERATURE MONITOR MASTERTEMP 6 WIRING DIAGRAM MASTERTEMP ...
Page 45: ...MONITOR DIGITAL TEMPERATURE MASTERTEMP 42 EXEMPLO DE APLICAÇÃO ...
Page 46: ...MONITOR DIGITAL TEMPERATURE MASTERTEMP 43 CÓDIGO DE CATÁLOGO DIMENSÕES ...
Page 47: ...MONITOR DIGITAL TEMPERATURE MASTERTEMP 44 DIAGRAMAS DE LIGAÇÃO MASTERTEMP ...