Installation manual
61
The use of power electronics (converter or filter for example) may lead to unexpected release of breakers with 30 mA
differential current device.
Therefore a Type B residual differential protection system with reinforced immunity of 300 mA in accordance with
standard NFC 15100 must be used for our washing machines.
To avoid these untimely activations, you ought to use differential protecting systems with residual current only, having
a high level of reinforced immunity as regards leakage transient current.
Pass the power supply cable of the machine through the stuffing box on the top of the machine.
Caution
The main switch must be removed in order to have easy access to the connections terminals.
Remove the outer sections (A) and the inner section (C) by unscrewing the screws (B). When the cables are at-
tached, reassemble the switch in reverse order.
For each machine, install a fixed multipolar circuit breaker (or fuses protector) in the laundry main cabinet.
d0466
Connect the power supply cable on the machine main switch. Connect the 3 phases on the main switch (see marks
L1, L2, L3) and connect the earth wire on the earth terminal (PE) of this main switch. (see chapter “Function checks”).