23
ENGLISH
Appendix(3)
The Minimum length pipe is 3m
Additional refrigerant required for pipe length greater than standard 7.5m installation can be
calculated using the following equation:
M = (F – 7.5) x R
Where:
M = Mass of additional refrigerant (g)
F = Final installed connecting pipe length (m)
R = Additional refrigerant required per meter of connecting pipe (g/m) (refer to the above table)
Example:
If the totel length (A) for 9K model is 10m, then the additional refrigerant need to fill by M:
M = (10-7.5) x 12 = 30g
Models
Gas Pipe
Diameter (mm)
Standard
Length (m)
Maximum
Length (m)
(A)
Maximum
Height (m)
(B)
Additional
Refrigerant
(g/m)
Liquid Pipe
Diameter (mm)
5
12
15
10
Ø9.52 (3/8")
Ø6.35 (1/4")
ESV09CRS-B2
ESV12CRS-B2
ESV09CRR-C6
ESV09CRR-C7