30
Installation manual
6.2
Machine connection with ferrite
6.2.1
Machines with AFC or DSC
To obtain approved level of EMC, it is mandatory to use the ferrite which is enclosed with machines equipped with
AFC (adaptive fan control) or DSC (drum speed control). (Note that this is only valid for those machines).
Before connecting to the machine, the protective earth (PE) wire shall be wrapped around the ferrite.
Prepare the power cord by making sure the protective earth (PE) wire is longer than the other wires according to the
table.
Wire size
L
x times through
AWG14 or 2,5 mm
2
280 mm
x 5
AWG12 or 4 mm
2
280 mm
x 5
AWG10 or 6 mm
2
300 mm
x 5
AWG8 or 10 mm
2
330 mm
x 5
AWG6 or 16 mm
2
400 mm
x 5
AWG4 or 25 mm
2
490 mm
x 5
L
fig.X01516
When the power cord has been prepared according to the table, wrap the protective earth (PE) wire through the fer-
rite and then connect all wires according to the following connection options.
T1
T2
T3
N1
N
L1
L2
L3
fig.X01360B
Summary of Contents for Lagoon TD6-14
Page 2: ......
Page 50: ......
Page 51: ......
Page 52: ...Electrolux Professional AB 341 80 Ljungby Sweden www electroluxprofessional com ...