64
Installation manual
4.5.3
TABLE 3 correction factors for different cable insulating materials :
Insulating material
Maximum working temperature range
Correction factor
PVC
70 ° C (158° F)
1
Natural or Synthetic Rubber
60° C (140° F)
0.92
Silicone Rubber
120° C (248° F)
1.60
4.5.4
TABLE 4 B2, C and E correction factors for cable grouping :
B2
C
E
Number of cables
Seated in Cable Duct
Wall fixing or Cable Trough
Cable Tray
1
1.00
1.00
1.00
2
0.80
0.85
0.87
4
0.65
0.75
0.78
6
0.57
0.72
0.75
9
0.50
0.70
0.73
4.5.5
Calculation
The total current included for usint Table 1 should be the maximum rated current for the machine divided by the prod-
uct of the different correction factors. Other correction factors may also be applied ; consult cable manufacturers.
Calculation : example
The machine has a rated current of 60 A
The ambient temperature is 45°C ; Table 2 gives a correction factor of 0.91.
Rubber cable insuant : Table 3 gives a correction factor of 0.92.
The cable is fixed directly to the wall (Column C), with 2 cables side by side. The Table 4 gives a correction factor of
0.85.
Total current : _____
60A
______=
84A
...........................0.91x0.92x0.85..............
Taking Column C in Table 1 (wall fixing), we obtain a minimum cable section of :
3x 25 mm²
4.5.6
Electrical Standard characteristics for IC6 48xx FFS
Machine
Type
Heating
Supply Voltage
Installed Power
Rated Intensity
Connection Cable
Section
Main Circuit
Breaker or
Fuse
4821
4821
Steam / Gas
Electric
380/415V 3+E 50–
60Hz
380/415V 3+E 50–
60Hz
1.75 kW
38.2 kW
5 A
45 A
4 X 2.5 mm²
4 x 16 mm²
3 x 16 A
3 x 63 A
4825
4825
Steam / Gas
Electric
380/415V 3+E 50–
60Hz
380/415V 3+E 50–
60Hz
2.9 kW
46.10 kW
5 A
67 A
4 X 2.5 mm²
4 x 16 mm²
3 x 16 A
3 x 80 A
4832
4832
Steam / Gas
Electric
380/415V 3+E 50–
60Hz
380/415V 3+E 50–
60Hz
3.2 kW
56.75 kW
5 A
82 A
4 X 2.5 mm²
4 x 25 mm²
3 x 16 A
3 x 100 A
Summary of Contents for IC6 48 FFS Series
Page 1: ...Installation manual Ironers IC6 48xx FFS Original language 10102059 EN ...
Page 2: ......
Page 19: ...Installation manual 19 ...
Page 33: ...Installation manual 33 Proceed in reverse order in case of transport of the machine ...
Page 38: ...38 Installation manual ...
Page 55: ...Installation manual 55 ...
Page 59: ...Installation manual 59 ...
Page 69: ...Installation manual 69 Important Adjustments should be made by qualified personnel only ...
Page 78: ......
Page 79: ......
Page 80: ...Electrolux Professional AB 341 80 Ljungby Sweden www electroluxprofessional com ...