Installation manual
47
3.5.5
Evacuation system if several dryers are connected to a common evacuation duct
(except gas heating machines):
If several ironers are installed with a common evacuation duct, the cross section of the evacuation duct must in-
crease as a function of the number of installed machines so that each of them operates at the same value of air
resistance..
Use elbows (and not Tees) to allow the air to pass forwards.
The simplified figure below shows the principle on which the evacuation duct shape is designed.
Number of ironers
D1
D2
D3
D4
Outlet diameter of the exhaust pipe in mm
150
225
315
450
Ventilation aperture required section in dm²
2
4
8
16
The indicated evacuation diameter is the dryer outlet diameter.
Cross-sections of ducts between dryers and the outside of the building must be designed taking account of the flow
and the allowable head loss on each machine and the routing of ducts (elbows and lengths).
Please call us if you are in any doubt about the layout of your exhaust device if you are modifying an existing
installation.
Summary of Contents for IC6 48 FFS Series
Page 1: ...Installation manual Ironers IC6 48xx FFS Original language 10102059 EN ...
Page 2: ......
Page 19: ...Installation manual 19 ...
Page 33: ...Installation manual 33 Proceed in reverse order in case of transport of the machine ...
Page 38: ...38 Installation manual ...
Page 55: ...Installation manual 55 ...
Page 59: ...Installation manual 59 ...
Page 69: ...Installation manual 69 Important Adjustments should be made by qualified personnel only ...
Page 78: ......
Page 79: ......
Page 80: ...Electrolux Professional AB 341 80 Ljungby Sweden www electroluxprofessional com ...