![Electro-Sensors Electry-Sentry 1 Installation & Operation Manual Download Page 8](http://html1.mh-extra.com/html/electro-sensors/electry-sentry-1/electry-sentry-1_installation-and-operation-manual_2379885008.webp)
5)
Do you need to use the Hour Meter?
A)
NO, the Hour Meter is not needed:
Skip User Variables
Var31
and
Var32
.
Skip
Var34
Hour_and_Speed_Command_Select
[unless you already set-up
Var34
for Speed
Monitoring - then leave
Var34
‘as-is’].
B)
YES, the Hour Meter is needed:
Set the following variables as needed:
Variable
Default
Value
User’s
Value
Var31
Hour_Meter_Warning_
Time
9000
Hours
Var32
Hour_Meter_
Maintenance_Time
9500
Hours
Var34
Hour_and_Speed_
Command_Select.
0000 = Maintained
Disable/Enable.
0001 = One-Shot Disable/Enable
with Disable = Closed
0002 = One-Shot Disable/Enable
with Disable = Open.
0000
Note: The Hour Meter increments and its discrete Green/
Yellow/Red LEDs light-up only if all of the following
are true:
·
If
Var31
is
non-zero.
(i.e.,
Var31
= 0000 disables the Hour Meter).
·
AND If in Normal Mode, not in Program Mode.
(i.e., Being in Program Mode disables the Hour
Meter).
·
AND If the Hour_and_Speed_Enable command
is present. (i.e., The Hour_and_Speed_Disable
command disables the Hour Meter).
If any one of these three prerequisites are NOT met, then
the Hour Meter does NOT increment hours, NOR do the
Hour Meter’s discrete Green/Yellow/Red LEDs light-up
as per the number of hours reached.
6)
Leave
Var35
Test Mode Select at the default value of
‘0000’, to operate the ES1 in the ‘real-live-data-mode’.
7)
Please see the Reference Section of the User Manual
for details of any of the UserVars.
8)
Please see the Reference Section of the User Manual
for details of the TBx terminal blocks (found on pages
18 and 19 of the Reference Section), or use the handy
diagram silkscreened into the back side of the Front-
Panel.
9)
For easy reference, log your user variable values in the
chart on the inside of the Electro-Sentry 1’s front cover.
Free Catalog and Application Assistance
1.800.328.6170
Website: www.electro-sensors.com
990-005500 Revision D