When
Var35
is set to a ‘0004’, then the ‘test-data-mode’
correspondence between the 8 digital switch/button inputs and
the 8 Relay outputs is shown in the table below.
(Momentarily closing the following Remote Switch Digital
Inputs or pressing the associated Front Panel button will
momentarily de-energize the following relay, otherwise the relay
is energized):
Input
Nomanclature
Relay
TB32
Hour_and_Speed_Disable command
8
TB33
Silence_Horn/Alarm_Reset
7
TB34
Hour_and_Speed_Enable command
6
TB31:
1-2
Aux_Hour_Meter_Reset or
HOUR_METER_RESET button on Front
Panel
5
TB31:
3-4
Aux_Test_Left_Side or
TEST_LEFT_SIDE button on Front Panel
4
TB31:
5-6
Aux_Test_Right_Side or
TEST_RIGHT_SIDE button on Front Panel
3
TB31:
7-8
Aux_Test_Speed or
TEST_SPEED button on Front Panel
2
TB31:
9-10
Aux_Silence_Horn/Alarm_Reset
1
CAUTION: Doing this Var35 test may cause actual system
alarms
.
Factory default for Var35 is 0000 for operate in ‘real-live-
data-mode’.
Var36.
Software Identification. (Read Only)
This variable shows which version of software is loaded into
the Electro-Sentry 1.
Var36
’s value is viewable only, with NO
changes allowed.
Note: The Software Identification is also shown for 2
seconds on the LCD display during power-up.