OPERATIONAL TIPS 

 

1.

 

Indicator lights – there is a set of four indicator lights on the front cover.  Figure 1 is a reproduction of the 
front decal giving definition and information for using these indicator lights.  

2.

 

Boiler Power

 green LED indicates 24-volt is present on the control board and is continuous on.  Off could 

mean no 240/208-volt power, open manual reset (vessel top), open fuse, or bad transformer.  Also indicates 
supply sensor condition (solid = good, pulse = faulty). 

3.

 

240/208-volt element power current flow can only be measured when the external operating thermostat is 
calling for heat.  There is a 30-second delay before stage 1 turns on, this allows the pump to circulate and 
sample temperature.  Stage 2 will depend upon the temperature differential at the sensor in the supply pipe, 
see page 9 sequence (assumes off-peak mode). 

4.

 

The operating thermostat heat call can be verified by the red

 

LED marked 

Thermostat Call

 located on front 

cover. 

5.

 

Electric Mode

 yellow LED is on when the boiler is not being load controlled (blue wires closed). 

6.

 

The 

190°F Auto Reset Limit

 red LED is on when the vessel top hi-limit switch is open. 

7.

 

Via a small pin jumper arrangement on the control board, the circulator pump can 
be a direct function of the “W” input 

or

 interrupted by the load control device (even 

though there is a W input).  This diagram illustrates this pin jumper arrangement.  
This unit is factory setup in the “W” position meaning the pump will always run as 
a direct function of “R” to “W” operating thermostat.  By simply moving this black 
2-position jumper to the “L” the pump will be turned off during load control 
interrupt. 

8.

 

At outlet temperatures of approximately 120

 F, the maximum system pressure should be approximately 18 

PSI (124 kPa).  If the PSI (or kPa) increase from cold water to operating hot water is more than 
approximately 3 to 4 PSI (20.6 to 27.5 kPa), the expansion tank is too small, or there is air in the system. 

9.

 

At the top of the vessel is a manual reset, 205° F, primary hi-limit.  This is behind the upper control board 
cover, at the top of the vessel.  At the end of the two red/blk wires there is a small red stem between the wire 
tabs.  This is the reset button. 

10.

 

Check for water leaks and repair as required. 

11.

 

If flow seems to be a concern, determine both inlet and outlet water temperature and apply GPM (L/min) 
formula detailed in previous section “Information/Water Flow Calculations”. 

 

AQUASTAT OPERATION 

 

Determine from floor tubing supplier design outline the desired floor temperature.  Typically this relates to 
floor covering and tube placement design.  Set the aquastat set point for desired warm water outlet. 
 
The front temperature set point is selected by a small screwdriver dial switch.  
 

 

Summary of Contents for Mini-Boiler EMB-S-1

Page 1: ...g systems This model includes factory installed temperature sensing staging Comment If this application is for traditional hydronic heating requiring temperatures greater than 160 F and capacities larger than shown above contact factory for other Electro Boiler product series In this approximate sizing the EB M model series is fully modulating and designed for temperatures up to 180 F The EB M and...

Page 2: ...g Staging Control 1 Room Thermostat Placement 1 Built In Temperature Control 2 Water Flow Calculation 2 Installation Requirements 2 Electric Supply 3 Clearances 3 Mechanical Installation 4 Electrical Hookup 5 Water Fill Procedure 6 Operational Tips 8 Troubleshooting Helps 9 Drawings BX305 BH310 UAW411 BL001 XX017 ...

Page 3: ...MB S 5 3 07 11 60 06 018 1 53 5 78 02 006 EMB S 7 4 78 18 06 12 036 2 39 9 03 06 01 EMB S 9 6 14 23 20 23 07 3 07 11 60 10 03 Note Head Loss based on 110 F return temperature TEMPERATURE SENSING STAGING CONTROL This model series is factory equipped with a digital supply water sensor and a staging controller The controller regulates the elements to maintain a preset maximum or preset operating temp...

Page 4: ...at least 15 minutes GPM Volts x Amps x 3 4 Example 240 volts x 36 amps x 3 4 29376 5 8 gpm 500 x Temp rise 500 x 10 degree rise 5000 INFORMATION WATER FLOW CALCULATIONS METRIC L min Volts x Amps x 3 587 Example 240 volts x 36 amps x 3 587 30991 68 20 57 L min 251 04 x Temp rise C 251 04 x 6 C rise 1506 24 INSTALLATION REQUIREMENTS 1 All installation work must be performed by trained qualified cont...

Page 5: ...actices for handling electrical sheet metal and material handling processes Use them ELECTRIC SUPPLY Model Volts Phase Watts Btu h Amps CB Element Stg 1 Stg 2 EMB S 1 120 1 60 Hz 1 100 3 753 9 2 1 EMB S 2 120 1 60 Hz 2 500 8 530 20 8 1 EMB S 4 120 1 60 Hz 5 000 17 060 41 7 1 1 EMB S 5 240 208 1 60 Hz 4 500 3 500 15 354 11 942 18 8 16 8 30A 1 EMB S 7 240 208 1 60 Hz 7 000 5 300 23 885 17 913 29 2 2...

Page 6: ... required This can be an air diaphragm tank as provided in the plumbing kit or a basic empty tank where air is compressed at the tank top Temperature Pressure Gauge Recommended to observe the operation of the system Actually a temperature gauge at the inlet and outlet is desirable Pressure Safety Valve This is required at the hot outlet and is furnished as a loose component with the boiler unit it...

Page 7: ...NNECTION TO THE CIRCUIT BREAKER TERMINALS AND INSIDE THIS PRODUCT S CABINET WARNING TO AVOID THE RISK OF ELECTRIC SHOCK OR DEATH WIRING TO THE UNIT MUST BE PROPERLY GROUNDED FAILURE TO PROPERLY GROUND THE UNIT CAN RESULT IN A HAZARD LEADING TO PERSONAL INJURY OR DEATH NOTE This model series is designed and equipped for 240 volt residential single phase If this unit is used on 208 volt energy capac...

Page 8: ...S 1 Unless the source water is unusually poor and or rust elements additives are not required It is recommended the water source as shown on drawing BX305 comes through the household water softener 2 Impurities within a closed loop hydronic boiler are considerably less damaging than the typical domestic water heater In a closed loop electric boiler the water impurities boil out and the system esse...

Page 9: ...he metal pipe and listen for air bubbles If the water flow is consistent and quiet the system is probably purged and water filled 9 Close the drain valve Open the inlet gate valve 10 The cold system pressure at the gauge should be approximately 10 to 14 PSI 11 Close water supply valve and disconnect water supply 12 Optional The circulating pump can be energized during this fill operation by having...

Page 10: ...W input or interrupted by the load control device even though there is a W input This diagram illustrates this pin jumper arrangement This unit is factory setup in the W position meaning the pump will always run as a direct function of R to W operating thermostat By simply moving this black 2 position jumper to the L the pump will be turned off during load control interrupt 8 At outlet temperature...

Page 11: ...same as a blown fuse no front panel boiler power green LED To reset this device simple press the red button Comment The hi limit auto reset red LED is only operational during an active heat call lower red LED on WARMFLO TEMPERATURE BYPASS TROUBLESHOOTING OR TESTING Adding a jumper between W screw terminal and tab marked E bypasses the temperature sensing and WarmFlo control In other words with the...

Page 12: ...EMB S H 12 04 18 1 of 2 BX305 ...

Page 13: ...EMB S H 12 04 18 2 of 2 BX305 ...

Page 14: ...EMB S EMB H 03 19 19 1 of 2 BH310 G ...

Page 15: ...EMB S EMB H 03 19 19 2 of 2 BH310 G ...

Page 16: ...DECAL TITLEBLOCK ...

Page 17: ...itional 4 enclosure and 40VA transformer Pumps EB ZEA8 with enclosure and 40VA transformer for 8 zone pumps Zone Valves EB ZTS 1 install within boiler cabinet encl option EB ZTS 2 add additional 4 enclosure and 40VA transformer EB ZES8 with enclosure no transformer for 8 zone valves ZONE CONTROLLER SWITCHING RELAY EE 5051 MULTI BOILER EB C STG5 This DPDT 24 volt switching relay provides a convenie...

Page 18: ...erature pressure gauge pressure relief safety valve and when applicable the WarmFloTM electronic control sensors These kits provide the additional components for easy installation 5585 Mini Boiler 10 kW TS Series 5586 TS Series Standard 5578 3 4 Pipe 5582 1 Pipe 5579 1 1 4 Pipe 120V 1 25 HP maintenance free wet rotor circulator Pump curve example 5 GPM 19 L 11 ft of head 32 9 kPa 120V 1 6 HP maint...

Page 19: ...acement Labor Allowance Schedule for a period of ninety 90 days from the date of original purchase to the original owner at the original installation site The Repair Replacement Labor Allowance is designed to reduce the cost of repairs This Repair Replacement Labor Allowance may not cover the entire labor fee charged by your dealer contractor TWENTY YEAR 20 LIMITED WARRANTY ON BOILER ELEMENTS AND ...

Page 20: ...ubject to adjustment upon verification of defect 2 Any product or product part that has been damaged as a result of being improperly serviced or operated including but not limited to the following operated during construction phase with insufficient water or air flow allowed to freeze subjected to flood conditions subjected to improper voltages or power supplies operated with air flow or water con...

Reviews: