06/07/2016 2
EI508
INSTALLATION REQUIREMENTS
1.
All installation work must be performed by trained, qualified contractors or technicians. Electro
Industries, Inc., sponsors installation and service schools to assist the installer.
Visit our web site at
electromn.com for upcoming service schools.
2.
All electrical wiring must be in accordance with national electric codes and local electric codes,
ordinances, and regulations.
3.
Observe electric polarity and wiring colors. Failure to observe could cause electric shock and/or
damage to the equipment.
4.
This unit can only be used for its intended design as described in this manual. Any internal wiring
changes, modifications to the circuit board, modifications or bypass of any controls, or installation
practices not according to the details of this manual will void the product warranty, the ARL
certification label, and manufacturer product liability. Electro Industries, Inc., cannot be held
responsible for field modifications, incorrect installation, and conditions which may bypass or
compromise the built-in safety features and controls.
SPECIFICATIONS - TABLE 1
Model Nominal
kW
Min.
CFM
Element
Cross Section
Source
CB
Internal
Fuse
Shipping
Weight
EM-WE1025H
9.6
40
1000
8 W x 10 D
50
N/A
12
EM-WE1535H
14.4
60
1500
8 W x 10 D
75
30 & 50
16
EM-WE2035H
19.2
80
2000
8 W x 10 D
100
50 & 50
19
EM-WE1025L
9.6
40
1000
8 W x 16 D
50
N/A
15
EM-WE1535L
14.4
60
1500
8 W x 16 D
75
30 & 50
19
EM-WE2035L
19.2
80
2000
8 W x 16 D
100
50 & 50
21
NOTE:
Model series EM-WE****C is the same element and control box assembly as model EM-WE****L except
prepackaged in a 16”w x 16”d plenum.
* Assumes 100
F inlet and all air passes through element rack. If duct/plenum is larger than element rack (without
factory deflector kit), the air volume external (passing around) to the element rack must be added to this CFM
requirement.
+ At 240 volt, single phase.