Doc
#
E180701
A-6
A: Removing a Meter from Service
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
A.2: Reinstalling the Meter
Follow this procedure to reinstall the meter:
1. Place meter in its location on the panel.
2. Tighten the 4 mounting screws.
3. Insert all connectors into the appropriate sockets on the meter.
4. Connect the 48 current leads to the meter making sure they are attached in the
proper order.
5. Install the 5 fuses in the fuse block in their proper location.
6. Unscrew all shorting screws on the CT connection block. See the figure below.
Figure A.5: Un-shorting the CTs
7. Verify that no foreign material remains inside the enclosure: clean it out if found.
8. Energize all circuits and verify operation.
TURN SCREWS COUNTER-
CLOCKWISE TO UNSHORT THE CT
Summary of Contents for Shark MP200