EDA-Z1000 - Installation and Operation Manual
3. User
Operation
Please note: No operator serviceable parts are contained within this panel. Always refer to a qualified technician
for parts and servicing.
3.1 System
Normal
In normal operation the screen will show either the date and time, contact details or alternate the two depending on the customers
requested settings. Also a single green “Supply” LED will be illuminated.
A.N.Other Fire
Thursday
01279 450185
25-05-2006
11:02:31
11:02:31
3.2 Fault
Conditions
If a fault occurs, a message describing the fault will be displayed and the internal buzzer will sound. This will detail the device type,
a description of the fault, the unit / device number and a location description (if programmed). The description has a maximum
length of 59 characters and will scroll across the screen. Appropriate action should be taken to remedy the fault as this may affect
the operation of the fire alarm system. If in doubt, the system maintenance company should be contacted.
001 SMOKE/SOUNDER 05
UNIT REMOVAL
1
st
Floor Garden Entr
If more than one fault exist on the system they will scroll round every 5 seconds. Pressing the cursor keys will automatically move
to the previous or next fault.
3.3
To Silence a Fault
Press ‘Silence Buzzer’.
Once the ‘Silence buzzer’ button has been pressed the panel assumes that the fault has been acknowledged and does not resound the
buzzer. If a different fault occurs, the panel will sound the buzzer until the new fault has been acknowledged.
3.4
To Reset a Fault
Assuming the fault has been rectified, pressing reset will reset the system and the system normal screen will be displayed. If the fault
is still present or re-occurs it will be re-displayed (this could take some time depending on the type of fault).
For a list of faults, their most common causes and ways to rectify faults see Appendix 2. Note that all faults will continue to be
displayed on the panel until the system is reset, even if the fault condition has been rectified.
3.5 Alarm
Conditions
If the Alarm sounds the premises should be evacuated. A screen will be displayed similar to below. The Fire LEDs will flash and the
appropriate zone LED(s) will flash. The first line details the first zone that has been activated and the last zone to activate. The
second line provides a count of all zones in alarm. The third line details the event number, device type and number. The last line
details the text location of the device in alarm. If the description is longer than 20 characters it will scroll across the screen. If more
than 1 event occurs, the bottom two lines will scroll.
First ZN:1 Last ZN:1
Zones in alarm:1
001 CALLPOINT 06
First Floor Next to W
Version Z1000/V1.05
Electro-Detectors