EDA-Z1000 - Installation and Operation Manual
Actuators
If actuators are not required to operate then set ‘Actuators’ to OFF. Actuators are output devices used to control equipment like
magnetic doors, other alarm systems, gas valve shut-offs, air conditioning etc. It would be normal for actuators to be isolated in an
alarm test.
Sound areas
Setting this to zero will sound all sounders providing the sounder option is on. By selecting a specific sound area a certain group of
sounders can be operated that are programmed to this area.
Fire Relay
If the fire relay inside the panel is required to be disabled this should be set to OFF. This is often used as a way of triggering a link to
the fire brigade or to an alarm monitoring station. Always follow the procedure outlined by the system installer.
Timeout
This is the amount of time before the system will automatically exit test mode operation. This should be set slightly longer than the
test should take. It can be set in 1 hour intervals and is selected using the cursor keys. A maximum of 48 hours can be set.
The user should now press enter to enable the test mode. The ‘Test Mode’ LED will illuminate.
Test Mode Enabled
Save Test Settings
YES
ENTER to Continue
Once test options have been selected these can now be saved for quick setup in the future. Once the test screen is entered the panel
will prompt to use saved settings, if unsure of the saved settings select NO and re-define the test parameters.
Devices that require testing should now be set into a fire condition and the details on the screen checked. Care should be taken to
ensure the correct devices are tested as failure to do this could result in all the bells sounding.
Once the tests are complete and the user is satisfied that everything functioned correctly, the test mode should be disabled. If this
procedure is forgotten the test mode will automatically time out after the selected period.
4.4
To Disable the Test Mode
Press the ‘MENU’ button, select ‘4 -Test Modes’ then ‘2 -Disable Test’ Press ‘ENTER’ to disable test. The ‘Test Mode’ LED will
extinguish.