EDA-R5000 Installation Manual  

Page 3 of 3 

                     Ref: EDA_R5000_Install_V104.doc  

 

Electro-Detectors

 

indicate a “verify fail” fault, because the panel has lost communication with the device, or a battery fault will be 
displayed.  Should either of these be witnessed, the batteries should be changed immediately.  If the unit detects a fault 
with the battery a ‘battery fault’ will be indicated on the panel.  Therefore:- 
 
1.

 

Remove the detector from the base by rotating the detector anti-clockwise and separating the unit. 

2.

 

Remove the power link. 

3.

 

Remove the back plate by removing the two screws 

4.

 

Remove the old battery pack. 

5.

 

Fit the new battery pack making sure the battery’s pins are lined up and pressed down. 

6.

 

Re-fit the back plate. 

7.

 

Press and hold the unit removal and reset button simultaneously. 

8.

 

With these buttons pressed down, fit the power link. 

9.

 

Let the unit go into its log-on mode, (it will beep) and keep the buttons pressed down. 

10.

 

After another 5 seconds a second BEEP will sound, at this point release the buttons.  This will re-set the battery 
counter after a further 15 minutes. If you realise that you didn’t want to reset the counter, then power the unit 
down by removing the power pin. Leave for 5 seconds and re-apply the power. The counter will not reset. 

11.

 

Refit the device onto its base. 

 

 
Faults displayed on the control panel from smoke detectors:- 

 

Low  Battery: 

The  batteries  are  approaching  their  end  of  life.    The  unit  will  continue  to  operate  for  a  further  60 

days within which time the batteries should be changed. 
 

Verify Fail: 

The panel has lost communication with the device, this could be caused by the batteries being flat, the 

unit failing to operate, something obstructing the radio signal path or the device not being installed correctly with an 
adequate signal strength. 
 

Battery Fault:

 The unit has detected a problem with the battery. 

 

Unit Removal: 

If the unit is removed from its base, the panel will display a unit removal/tamper fault. 

 

Tx/Rx Fault: 

A failure with the transmit / receive module of the device. It is suggested that the fault should be reset 

and if the same fault occurs within 60 minutes the unit be replaced. 
 

Int Fault:

 The unit has detected an internal problem with the way it is operating. There are several faults that can 

cause this but the usual way of solving the problem is to replace the unit or return it for repair. It is suggested that 
the fault should be reset and if the same fault occurs within 60 minutes the unit be replaced. The faults can relate to 