background image

D450-15-00

1

I56-725-04

B524BI and B224BI Plug-in Isolator

Detector Bases

For use with the following smoke detectors:
In US:

B524BI:

1551, 2551, 2551T, 5551, 5551R

B224BI:

1251, 2251, 3251

INSTALLATION AND MAINTENANCE INSTRUCTIONS

A Division of Pittway

 3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

Before Installing

Please thoroughly read the system wiring and installation
manuals, and manual I56-407, 

Guide for Proper Use of Sys-

tem Smoke Detectors,

 which provides detailed information

on detector spacing, placement, zoning, and special appli-
cations. Copies of these manuals are available at no charge
from System Sensor.

NOTICE:

 This manual should be left with the owner/user

of this equipment.

IMPORTANT:

 The detectors used with these bases must be

tested and maintained following NFPA 72 requirements.
The detectors used with these bases should be cleaned at
least once a year.

General Information

Isolator bases prevent an entire communications loop from
being disabled when a short circuit occurs. They accom-
plish this by isolating that part of the loop containing the

Specifications

Base Diameter:

6.2 inches (157 mm)

Base Height
     B224BI:

1.2 inches (31 mm)

     B524BI:

1.4 inches (36 mm)

Mounting:

4-inch square box with or without plaster ring, Min. depth - 1.5 inches (13 mm)
4-inch octagon box, Min. depth - 1.5 inches (13 mm)
3-1/2-inch octagon box, Min. depth - 1.5 inches (13 mm)

Operating Temperature Range:

–10

°

C to +60

°

C (14

°

F to 140

°

F)

NOTE: Do not install in locations where normal ambient temperature

   extends beyond 0

°

 to 49

°

C (32

°

 to 120

°

F)

Operating Humidity Range:

10% to 93% Relative Humidity (Non-condensing)

Electrical Ratings

Operating Voltage:

15 to 28 VDC

Current
      Standard:

450

µ

A Maximum

      Alarm:

5mA Maximum

short from the remainder of the circuit. These bases also
automatically restore the entire loop when the cause of the
short circuit is corrected. In general, up to 25 addressable
devices may be isolated between isolator bases. For the
purposes of determining the number of devices between
isolator bases, one 3251 is equivalent to 12 addressable de-
vices. For example, (13) 2251’s and (1) 3251 may be
grouped between two isolator bases.

Mounting

The detector base mounts directly to 3

1

/

2

- and 4-inch octa-

gon and 4-inch square boxes, with or without a plaster
ring. To mount, remove the decorative ring by rotating it in
either direction to unhook the snaps. Then, separate the
ring from the base. Install the base on the box, using the
screws supplied with the junction box and the appropriate
slots in the base. Replace the decorative ring on the base
and rotate it in either direction until the ring snaps in place
(see Figure 1).

Summary of Contents for B224BI

Page 1: ... inch square box with or without plaster ring Min depth 1 5 inches 13 mm 4 inch octagon box Min depth 1 5 inches 13 mm 3 1 2 inch octagon box Min depth 1 5 inches 13 mm Operating Temperature Range 10 C to 60 C 14 F to 140 F NOTE Do not install in locations where normal ambient temperature extends beyond 0 to 49 C 32 to 120 F Operating Humidity Range 10 to 93 Relative Humidity Non condensing Electr...

Page 2: ...l interference NOTE Detector head power is supplied by terminals 1 and 2 Therefore the head will be part of this isolation group If shielded cable is used the shield connection to and from the detector must be continuous by using wire nuts crimp ing or soldering as appropriate for a reliable connection Alarm system control panels have specifications for allow able loop resistance Consult the contr...

Page 3: ...n the screwed down position A label is affixed to the base for recording the zone ad dress and type of detector being installed at the base loca tion This information is useful for setting the detector head address and for verification of the sensor type required for that location Once all detector bases have been wired and mounted and the loop wiring has been checked the detector heads may be ins...

Page 4: ...detecting a smoldering fire with either an ionization type detector or a photoelectric type detector Either one of them may alarm only after flaming has initiated which will generate the heat needed to drive the smoke to the ceiling Smoke from fires in chimneys in walls on roofs or on the other side of a closed door s may not reach the smoke detector and alarm it A detector cannot detect a fire de...