Radio Fire Alarm System – User Manual
Page:
13
V301_user Feb 2009
Electro-Detectors
4.1 Main Panel Power Supply Board Connections (EDA-M100/M150/M200)
Connectors and Terminals
CON1
To Receiver Unit
CON2
To Processor Board
CON3
To Expansion Board
T1
External Supply Ground
T2
External Supply 24V In
T3
Battery Ground
T4
Battery 12V In
T5
Printer Ground
T6
Printer 5V
T7
External Call Point Input Gnd
T8
External Call Point Input 5 V
T9
Ground
T10
External Monitor In
T11
External 24 V Output
T12
External Ground
T13
Auxiliary Relay 1 Common
T14
Auxiliary Relay 1 Norm Closed
T15
Auxiliary Relay 1 Norm Open
T16
Fault Relay 2 Common
T17
Fault Relay 2 Norm Closed
T18
Fault Relay 2 Norm Open
T19
Sounder Relay 1 Alarm +
T20
Sounder Relay 1 Alarm -
T21
Sounder Relay 2 Alarm +
T22
Sounder Relay 2 Alarm -
T23
AC In 18V RMS
T24
AC In 18V RMS
LK1
Antenna Monitoring
LK2
Antenna Monitoring
Fuses
F1
0.5A
Sounders and External 24V Supply
F2
3.15A
Main 5V Power Supply to Processor
F3
6.3A
Battery
F4
3.15A
Printer (Control Panel Only)
F5
0.5A Battery
Charger
F6
6.3A
24 External Supply Input (Control Panel Only)
F7
0.5A
Sounder Circuit 2
F8
0.5A
Sounder Circuit 1