Specifications

 

and

 

tolerances

 

 

RCD TEST TOLERANCES 

 

Supply Voltage Range 

195 to 253V AC 50-60Hz 

Nominal Currents 

10mA,30mA,100mA 

Test Current Accuracy x 1/2 

+0% - 10% 

Test Current Accuracy x 1 

+10% -0% 

Test Current Accuracy x 5 (30mA only) 

+/- 5% 

Test Current Accuracy Ramp 

+/- 5% of rated 

I

N

 

Trip Time Accuracy to 1.999s 

+/- (1% +1ms) 

Fault / Touch Voltage 

50V 

Over Voltage Protection 

440V 

 

RCD Trip Time  

 

Measurement Range

 

5ms – 1999ms 

Operating Range Per EN61557 

38ms – 1999ms 

Standards  

To meet 300V CATIII  

The AUTOTRIP complies fully with the requirements of EN61010 and complies with 
the sections of EN61557, Electrical Safety in Low Voltage Systems up to 1000V AC 
and 1500V DC as listed below. 

 

BS EN 61010-2-030:2010 (Safety) 

 

BS EN 61326-2-2:2013 (EMC) 

 

BS EN 61557-1:2007 (General performance) 

 

BS EN 61557-6:2007 (RCD performance) 

Environmental 

Operating Temperature Range  

 

0

C to 40

Storage Temperature Range  

 

-10

C to 60

Operating Humidity 

 

 

80% @ 31

C to 50% @40

 

 

 

 

 

Summary of Contents for AUTOTRIP

Page 1: ...AUTOTRIP RCD TESTER USER MANUAL...

Page 2: ...ty of the protective earthing conductors and equipotential bonds before carrying out RCD testing Do not operate the meter around explosive gas vapor or dust Do not apply more than the rated voltage 30...

Page 3: ...f and disconnect from any electrical circuits Remove test leads Remove the small crosshead screw on the back of the instrument that retains the battery cover and fit four Alkaline batteries type AA LR...

Page 4: ...n which the tester is primed to automatically start the test as soon as the probes are connected to a circuit thereby leaving your hands free to hold the test probes Socket wiring check To protect bot...

Page 5: ...d set that can be fitted with either prod tips or crocodile clips as required The 3 colour coded prods crocodile clips of the test lead should be connected to the corresponding Line Neutral and Earth...

Page 6: ...indicator is not able to determine N PE supply reversal If all is well the VOLTAGE POLARITY warning LED will light Green and the supply voltage will be displayed in the primary display area In the ev...

Page 7: ...tion time of 40ms when a fault of five times itsrated current is introduced This is referred to as the x5 test For the reasons explained below all of the above tests have to be conducted at both 0 and...

Page 8: ...S When first connected to a mains supply the AUTOTRIP will automatically conduct a safety test to ensure that the Live Neutral and Earth conductors are all connected correctly and that the supply vol...

Page 9: ...on to conduct a test at the x1 setting at 0 The result will be shown as a pass if a 30mA RCD trips within 300ms After displaying the result for a few seconds the tester will switch to the 180 phase po...

Page 10: ...be recalled by using the RECALL button to cycle through the routine The AUTOTRIP will also indicate whether it has passed or failed the RCD requirements 30mA Full Auto Test Turn the rotary selector t...

Page 11: ...CD Trip Time Measurement Range 5ms 1999ms Operating Range Per EN61557 38ms 1999ms Standards To meet 300V CATIII The AUTOTRIP complies fully with the requirements of EN61010 and complies with the secti...

Page 12: ...air and calibration please contact place of purchase Electrical Factory Outlet Pty Ltd PO Box 701 Rochedale South QLD 4123 PH 61 7 3411 0303 E mail sales electricalfactory com au www electricalfactory...

Reviews: