6

KEYBOARD DESCRIPTION

Instrument programming can be carried out on the keyboard located on the instrument’s front
panel. The keys for displaying the measurements, consumptions, temperature and the clock calendar
each have a green LED which lights up when that function is utilised. The L1, L2 and L3 keys each
have a red LED which lights up when that function (display of the phase measurements) is utilised.

KILO  3 PHASE ENERGY ANALYZER/CONTROLLER

?

Key for access to programming and reset

?

High luminosity display (adjustable)

?

Key for phase selection (cursor keys during programming)

?

Key for displaying the calendar/clock and the temperature

?

Key for displaying the consumption of Three-phase Reactive Energy (kVArh) and of the
auxiliary contacts

?

Key for displaying the consumption of Three-phase Active Energy (kWh)

?

Key for displaying Three-phase instantaneous, average and peak Apparent Power
(VA)measurements and the three-phase instantaneous Reactive Power (VAr)

?

Key for displaying three-phase instantaneous, average and peak Active Power (W)
measurement and Power Factor (Cos f)

?

Key for Voltage and Current display

6.1

MEASUREMENT RELATED FUNCTION PROGRAMMING

The writing “ELECTREX” appears when the instrument is powered. After a few seconds the
voltage and current measurements will be displayed (the LED on the key is lighted). To enter
into programming mode, press simultaneously the programming access key (see Fig.18) and
the key.

                        

KILO

   3 PHASE ENERGY

The default settings provide:
- Low voltage measurement
- 4-wire connection (STAR)
- CT  ratio = 1
- Integration time = 15 minutes

6.1.1 measurement functions SELECTION

The instrument can carry out measurements on both low and high voltage. The display will
show the first selection (direct measurements in low voltage):

By pressing the key 

  the second selection will be displayed (measurements in high

voltage with VTs):

Press the key  

  on the page selected and proceed to program the other functions.

6.1.2 VT  TRANSFERTION RATIO MEASUREMENTS HIGH VOLTAGE

SELECTION

Select “VOLT HIGH” to access the programming page which enables the setting of the
transformation ratio of the VT utilised. The display will show:

 

The key 

  increases the digit to be set (flashing).

The key 

  decreases the digit to be set (flashing).

The key  

    enables moving from one digit to another (from the more significant digit to

the less significant digit). Once the last digit is set, this key enables programming of the
transformation ratio of the VT and access to the next programming page.

6.1.3 CONNECTION TYPE SELECTION (STAR OR DELTA)

Selecting“VOLT LOW” on the first programming page or after setting the VT ratio, (having
selected “VOLT HIGH” on the first measurement page) select the type of connection.  The
instrument can be connected to 4-wire networks (CONN    4W) or three wire networks (CONN
D  3W). The display will show:

By pressing the key 

 the second selection will be displayed:

Press the key 

  on the page which contains the connection wanted and proceed to the

programming of the other functions.

6.1.4 CT TRANSFERTION RATIO SELECTION

After selecting the type of connection (star or delta) the CT transformation programming page
appears. The display will show:

The key 

 increases the digit to be set (flashing).

The key 

 decreases the digit to be set (flashing).

The key  

 enables moving from one digit to another (from the more significant digit to

the less significant digit). Onced the last digit is set, this key enables programming of the CT
transformation ratio and access to the next programming page.

6.1.5 AVERAGE POWERS INTEGRATION TIME SELECTION

The last programming page enables the setting of the integration time (in minutes) on which
the averages of Active Power and Apparent Power will be calculated. The display will show:

The key 

 

  increases the digit to be set (flashing).

The key 

  decreases the digit to be set (flashing).

The key   

    enables moving from one digit to another (from the more significant digit

The key for access to
prgramming is located under
the writing "ELECTREX"
between the letters E and L

5

RS485 CONNECTION

The instrument has three terminals for connection to the RS485 port. The connection must be
carried out using a twisted pair inserted in the appropriate screw terminals (see Fig. 16). The
terminals marked "A" and "B" indicate the polarity of the contacts. There is also a terminal identified
by the symbol   

    for connecting the shield (sheath) of the twisted pair to be used for network

installation in high interference environments or in the presence of strong currents. The polarity of
the contacts must be observed when the connection is made (see also the indications on the label).

It is recommended to use a twisted pair cable with minimum section of 0,36 mm

2

 (22 AWG)

characteristic impedence 120W and with capacity lower than 60 pF/m.

Flashing digit

Flashing digit

Flashing digit

English

Instructions

Summary of Contents for KILO

Page 1: ...rs whenever the instmrument must be opened it must be disconnected from all power sources The instrument s capacitors may still be charged even after it has been disconnected from all power sources Maintenance and or repairs must be carried out only by qualified authorized personnel If there is ever the suspicion that safe use is no longer possible the instrument must be taken out of service and p...

Page 2: ...current output as indicated in the drawings Fig 7 1 and 7 2 Advanced Functions If the instrument has been programmed for Cogeneration mode connection of the CTs must be carried out as indicated in the drawings in Fig 10 1 and Fig 10 2 located on the next page 4 2 CONNECTION ON UNBALANCED THREE PHASE 4 WIRE NETWORKS The drawing in Fig 10 indicates how to make the current connections with 3 CTs 4 2 ...

Page 3: ...e set flashing The key enables moving from one digit to another from the more significant digit to the less significant digit Once the last digit is set this key enables programming of the transformation ratio of the VT and access to the next programming page 6 1 3 CONNECTION TYPE SELECTION STAR OR DELTA Selecting VOLT LOW on the first programming page or after setting the VT ratio having selected...

Page 4: ...to be set flashing The key enables moving from one digit to another from left to right Once the last digit is set it enables confirmation of the programming and to access to the selection page of the surveyed temperature measurement unit 6 2 6 WEEK DAY SETTING This function is available on KILO M only ad it is fundamental for recording in memory the weekly consumtion The data are stored in memory ...

Reviews: