KILO

KILO M

Fig. 10

Fig. 9

Fig. 12

Fig. 11

Fig. 13

Fig. 14

C 1 2

C

= Common

1

= Meter 1

2

= Meter 2

Min Pulse 5 mSec.

INSTRUMENT

INTERIOR

INSTRUMENT

ESTERIOR

Connection to voltage-free

contacts

Connection to open-collector transistor

4.4

ALARMS CONNECTION

There are two alarms which drive two relays, the  terminals are internally connected to
noramlly open voltage free contacts of an opto-mos (solid state relay) rating 250 VDC, 100mA.
Use cables with max. gauge 4 mm

2

 for the terminal connections (see Fig. 15).

C

   = Common

NO

 

= Normally  Open

C   NO       C  NO

Fig. 15

Fig. 7-1

Fig. 7-2

Fig. 8-1

Fig. 8-2

Current signal connection

with 2 CTs (L1 and L2)

Current signal connection

with 2 CTs (L1 and L3)

Connection of 2 CTs in Cogeneration mode

The drawing in Fig. 6 indicates how to make the current connections with 3 CTs. The Fig. 7-
1 and 7-2 indicate how to connect current signal using 2 CTs (Phase L1 and L2 or Phase L1
and L3).

CAUTION:

 In case of connection of 2 CTs it is absolutely  essential  to respect the sense

(orientation) of the CTs current output as indicated in the drawings (Fig. 7-1 and 7-2).

Advanced Functions:

  If the instrument has been programmed for Cogeneration mode,

connection of the CTs must be carried out as indicated in the drawings in Fig.10-1 and Fig.10-
2 located on the next page.

       

4.2   CONNECTION ON UNBALANCED THREE-PHASE 4 WIRE NETWORKS

                    

The drawing in Fig.10 indicates how to make the current connections with 3 CTs.

4.2.1 HIGH VOLTAGE THREE PHASE WIRES DELTA NETWROK WITH CT's

AND VT's

L1

L3

L2

L1
L2
L3

   

L1

L3

L2

L1
L2
L3

L1

L3

L2

L1
L2
L3

WARNING:

 In Fig. 12 and 13 any one of the delta vertices may be earthed.

For  the connection of CTs in medium or high voltage networks, follow  the same procedure
described for low  voltage connections.

4.3

CONNECTION OF THE AUXILIARY METERS

The instrument has two digital inputs to which two external meters can  be connected (for
example, a water meter and a gas meter).
The digital inputs are optoisolated and   internally  power supplied (12 ÷ 18 VDC 1,3 KOhm)
and can count pulses with a maximum frequency of 100 Hz.
The connection must be carried out using cables with max. gauge 4 mm2 to be inserted in the
terminals indicated below in Fig.14.

Voltage signal connection with 3 VTs

Voltage signal connection with 2 VTs

Voltage signal connection with 2 VTs

English

Instructions

Voltage signal connection

Current signal connection

Summary of Contents for KILO

Page 1: ...rs whenever the instmrument must be opened it must be disconnected from all power sources The instrument s capacitors may still be charged even after it has been disconnected from all power sources Maintenance and or repairs must be carried out only by qualified authorized personnel If there is ever the suspicion that safe use is no longer possible the instrument must be taken out of service and p...

Page 2: ...current output as indicated in the drawings Fig 7 1 and 7 2 Advanced Functions If the instrument has been programmed for Cogeneration mode connection of the CTs must be carried out as indicated in the drawings in Fig 10 1 and Fig 10 2 located on the next page 4 2 CONNECTION ON UNBALANCED THREE PHASE 4 WIRE NETWORKS The drawing in Fig 10 indicates how to make the current connections with 3 CTs 4 2 ...

Page 3: ...e set flashing The key enables moving from one digit to another from the more significant digit to the less significant digit Once the last digit is set this key enables programming of the transformation ratio of the VT and access to the next programming page 6 1 3 CONNECTION TYPE SELECTION STAR OR DELTA Selecting VOLT LOW on the first programming page or after setting the VT ratio having selected...

Page 4: ...to be set flashing The key enables moving from one digit to another from left to right Once the last digit is set it enables confirmation of the programming and to access to the selection page of the surveyed temperature measurement unit 6 2 6 WEEK DAY SETTING This function is available on KILO M only ad it is fundamental for recording in memory the weekly consumtion The data are stored in memory ...

Reviews: